UNINTENDED EQUIPMENT OPERATION
Do not exceed any of the rated values in the characteristic table.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
|
Characteristic
|
Value
|
|
---|---|---|
Number of outputs per channel
|
One 24 Vdc source 0.5 A
|
|
Output voltage
|
19.2...30 Vdc
|
|
Minimum load current
|
None
|
|
Maximum load current
|
Each Point
|
0.5 A
|
Per Module
|
1.0 A
|
|
Off state leakage/point
|
-0.1 mA maximum
|
|
On state output voltage drop
|
3.0 Vdc maximum
|
|
Short circuit output current
|
(each point) 1.5 A maximum
|
|
Surge current maximum
|
Self-limiting per channel
|
|
Maximum load capacitance
|
50 μF
|
|
Maximum load inductance
L = load inductance (Henry)
I = load current (A)
F = switching frequency (Hz)
|
0.5 Henry at 4 Hz switching frequency
L = 0.5 / (I² x F)
|
|
Maximum frequency
|
10 kHz with load = 2 kΩ.
NOTE: To be considered when the OutputBlock parameter is set to Scaling Pulse.
For more detail, refer to the module functionality Reflex Output Block Function. |
|
Output protection (internal)
|
Transient voltage suppression
|
|
Short circuit
|
Short circuit protection of the output with breakdown
|
|
Polarity of output
|
By default
|
Logical 0 provides 0 V
|
Configurable setting
|
Applied when the module is operating without any detected fault
|
|
Fallback policy
|
By default
|
Apply 0
|
Configurable setting
|
Applied to the output when the module has lost the communication or PLC Stop or Halt.
Apply 0, 1 or maintain the last value
|