Output Characteristics
Original instructions
Output Characteristics
WARNING
UNINTENDED EQUIPMENT OPERATION
Do not exceed any of the rated values in the characteristic table.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
The following table presents the digital output characteristics:
Characteristic
Value
Number of outputs per channel
One 24 Vdc source 0.5 A
Output voltage
19.2...30 Vdc
Minimum load current
None
Maximum load current
Each Point
0.5 A
Per Module
1.0 A
Off state leakage/point
-0.1 mA maximum
On state output voltage drop
3.0 Vdc maximum
Short circuit output current
(each point) 1.5 A maximum
Surge current maximum
Self-limiting per channel
Maximum load capacitance
50 μF
Maximum load inductance
L = load inductance (Henry)
I = load current (A)
F = switching frequency (Hz)
0.5 Henry at 4 Hz switching frequency
L = 0.5 / (I² x F)
Maximum frequency
10 kHz with load = 2 kΩ.
NOTE: To be considered when the OutputBlock parameter is set to Scaling Pulse.
For more detail, refer to the module functionality Reflex Output Block Function.
Output protection (internal)
Transient voltage suppression
Short circuit
Short circuit protection of the output with breakdown
Polarity of output
By default
Logical 0 provides 0 V
Configurable setting
Applied when the module is operating without any detected fault
Fallback policy
By default
Apply 0
Configurable setting
Applied to the output when the module has lost the communication or PLC Stop or Halt.
Apply 0, 1 or maintain the last value