UNINTENDED EQUIPMENT OPERATION
Do not operate this equipment outside of its specified temperature range.
Failure to follow these instructions can result in injury or equipment damage.
|
![]() |
UNINTENDED EQUIPMENT OPERATION
Do not exceed any of the rated values in the characteristic table.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
|
Characteristic
|
Value
|
|
---|---|---|
Counter-channel number
|
2
|
|
Maximum input frequency
|
500 kHz
|
|
I/O Channels per counter
|
Number of digital inputs per channel
|
Two:
|
Number of digital outputs per channel
|
One 24 Vdc 0.5 A.
|
|
Hot swapping supported
|
Yes
|
|
Encoder Compliance
|
Complies to incremental encoder
|
|
Power distribution to sensors or encoders
|
Voltage: 24 Vdc (from field power supply input)
Current: Maximum 300 mA
|
|
Back plane power consumption
|
+3.3 Vdc
|
Typical: 150 mA
Maximum: 200 mA
|
+24 Vdc
|
Typical: 25 mA
Maximum: 30 mA
|
|
Dielectric strength
|
Between field and bus or ground
|
1400 Vdc for 1 minute
|
Between differential interfaces
|
1000 Vdc for 1 minute
|
|
Between inputs and outputs
|
1000 Vdc for 1 minute
|
|
Insulation resistance
|
> 10 MΩ
|
|
Field power supplies
|
Voltage
|
19.2...30 Vdc (24 Vdc Typical)
|
Current
|
It depends on the field sensors and the load of reflex output consumption.
For module operating: 30 mA.
|
|
I/O Diagnostics
|
Power supplies
|
Input or output not supplied
|
Input
|
Wrong connection with MPU sensor
|
|
Output
|
Overload or short circuit
|