Technical characteristics of As-i V2 bus
(Original Document)
AS-i V2 Bus
Technical Characteristics:
Characteristic
Value
Maximum cycle time of bus:
  • - 1 to 19 slaves = 3ms,
  • - 20 to 62 slaves = (1+n)*156μs
    where n = number of active slaves.
5 ms for 31 standard or extended address setting slaves,
10 ms for 62 extended address setting slaves.
Maximum number of slaves on the bus:
31 standard address setting slaves, or,
62 extended address setting slaves.
Maximum length of AS-i bus cables:
all branches without repeater
with two repeaters
100 meters
300 meters
Maximum number of I/O managed by the bus
standard address setting slaves: 124 inputs +124 outputs
extended address setting slaves: 248 inputs + 186 outputs
Nominal bus supply voltage
30 V DC
TSX SAY 1000 Module
Technical Characteristics:
Characteristic
Value
Programming the TSX SAY 1000 module
Control Expert
Response time with 31 slaves (1) for a PLC cycle time of 10 ms
Typically 27 ms, 37 ms maximum
Power consumption 5V PLC
Typically 100 mA / 150 mA maximum
Power consumption on 30 V AS-i/AS-i
Typically 50 mA / 60 mA maximum
Power dissipation
2.5 W max.
Protection against polarity inversion on bus inputs
Yes
Degree of protection
IP20
Isolated voltage
500 V DC
Operating temperature
0 to 60 degrees Celsius
AS-i master profile
M2e
Standards and service conditions
Compliant with those for Premium PLCs (See installation manual for Premium/Atrium PLCs)
(1) Logical response time + time between an AS-i input activated on the bus, processed in the PLC application and applied to an AS-i output.