Characteristic
|
Value
|
---|---|
Maximum cycle time of bus:
|
5 ms for 31 standard or extended address setting slaves,
10 ms for 62 extended address setting slaves.
|
Maximum number of slaves on the bus:
|
31 standard address setting slaves, or,
62 extended address setting slaves.
|
Maximum length of AS-i bus cables:
all branches without repeater
with two repeaters
|
100 meters
300 meters
|
Maximum number of I/O managed by the bus
|
standard address setting slaves: 124 inputs +124 outputs
extended address setting slaves: 248 inputs + 186 outputs
|
Nominal bus supply voltage
|
30 V DC
|
Characteristic
|
Value
|
---|---|
Programming the TSX SAY 1000 module
|
Control Expert
|
Response time with 31 slaves (1) for a PLC cycle time of 10 ms
|
Typically 27 ms, 37 ms maximum
|
Power consumption 5V PLC
|
Typically 100 mA / 150 mA maximum
|
Power consumption on 30 V AS-i/AS-i
|
Typically 50 mA / 60 mA maximum
|
Power dissipation
|
2.5 W max.
|
Protection against polarity inversion on bus inputs
|
Yes
|
Degree of protection
|
IP20
|
Isolated voltage
|
500 V DC
|
Operating temperature
|
0 to 60 degrees Celsius
|
AS-i master profile
|
M2e
|
Standards and service conditions
|
Compliant with those for Premium PLCs (See installation manual for Premium/Atrium PLCs)
|
(1) Logical response time + time between an AS-i input activated on the bus, processed in the PLC application and applied to an AS-i output.
|