It is possible to insert a device into an existing AS-i configuration without having to use the pocket programmer.
This operation is possible once:
-
-
A single slave is absent in the physical configuration
-
The slave which is to be inserted is specified in the Control Expert configuration
-
The slave has the profile expected by the configuration
-
The slave has the address 0
The AS-i module will therefore automatically assign to the slave the value predefined in the configuration.
The following table shows the procedure for making the automatic insertion of a new slave effective.
Step
|
Action
|
1
|
Add the new slave in the configuration screen in offline mode.
|
2
|
Carry out a configuration transfer to the PLC in online mode.
|
3
|
Physically link the new slave with address 0 to the AS-i bus.
|
NOTE: A project can be modified by carrying out the above manipulation as many times as necessary.