Communication Interruptions
Communication interruptions between the CPU and BMX EIA 0100 module are caused by the following:
-
Triggering of the processor watchdog if the BMX EIA 0100 is positioned in the rack holding the processor.
-
Disconnection of the X Bus cable if the BMX EIA 0100 module is positioned in an extension rack.
-
Removal of the BMX EIA 0100 power supply
-
Inoperative CPU
For these types of interruptions, the BMX EIA 0100 enters the OFFLINE mode and the CPU stops communication with the BMX EIA 0100.
NOTE: If the problem is on the X Bus, the CPU also indicates a detected error on the X Bus.
AS-Interface Power Interruptions
If the AS-Interface bus power is interrupted, then:
The BMX EIA 0100 indicates the error by turning off the front panel green ASI PWR LED and turning on the red FAULT LED.
The CPU indicates that all slaves values are invalid.
In the CPU memory image:
-
Digital input values are set to 0
-
For Analog slaves that adhere the AS-Interface Complete Specification standard, the values are 7FFF hex.
Break in the AS-Interface Medium
There are several places where break in the medium can occur:
-
After the
BMX EIA 0100 module, but before the AS-Interface power supply. The behavior is the same as
AS-Interface Power Interruptions. The
BMX EIA 0100 does not “see” the power supply.
-
The break is after the
BMX EIA 0100 and the AS-Interface power supply. All slaves
disappear from the front panel, but the
BMX EIA 0100 does not report a power supply interruption because it still “sees” the power supply.
-
The break is after the module and after one or more of the slaves. The slaves located after the break
disappear from the front panel. No power supply error is reported.
When a slave is removed (or quits functioning) from an active AS-Interface bus without changing the LPS (List of Projected Slaves, configured slaves), then from the point of view of the BMX EIA 0100 bus master, the slave disappears because the module is no longer able to exchange data with the slave. The BMX EIA 0100 then:
The detected configuration error is reported to the CPU using the Config_OK flag.
The CPU, in the case of a slave disappearance, indicates that:
There are 3 slave configuration errors that can be detected by the BMX EIA 0100:
-
A slave is detected but not projected, i.e., not in the configuration downloaded from the processor
-
A slave is projected but not detected, i.e., an expected slave is not detected
-
A Slave is projected and detected, but the configured profile is not the same as that of detected profile
A detected configuration error is reported to the CPU using the Config_OK flag and is indicated in the Module Fault tab of the channel diagnostic window.