Front Panel Diagnostic LEDs
Original instructions
Introduction
The state of the module is indicated by 4 LEDs in the upper display panel: RUN, ERR, A/B and I/O. Their state, Off, On or Flashing, provides information about the operating mode of the module.
The /B LED indicates which bank is displayed.
The LEDs 0 to 31 provide information about each slave on the bus at the indicated address.
Two additional LEDs labeled ASI PWR and FAULT provide information about the AS-Interface power supply and detected errors on the bus or a slave.
RUN, ERR and I/O LEDs
The combinations of these RUN (green), ERR (red) and I/O (green) LEDs indicate the different states of the module:
RUN
ERR
I/O
Status of Module
Off
Off
Off
Under-voltage or LEDs non-functional
Flashing
Off
Off
Waiting for the module configuration download
Flashing
Flashing
Flashing
Self tests
Off
Flashing
Off
Module is not correctly configured
On
Off
Off
Normal running mode (in the Protected Mode with data exchange on the bus)
Off
On
Off
Detected internal module error
On
Off
On
Detected error in the AS-Interface application (bus or slave)
On
Flashing
Off
Communication error detected with the PLC
/B LED
This green LED indicates which bank the LEDs 0 to 31 represent:
A/B
Slaves Displayed
Off
Bank A (standard and extended slaves)
On
Bank B (only extended slaves)
LEDs 0 to 31
These green LEDs provide information about the slaves with addresses 0 to 31 on the AS-Interface bus:
Slave Address LED
Slave Status
Off
Slave not configured and not detected
On
Slave active (configured, detected and activated)
Flashing Slow
Peripheral error detected on slave
Flashing Fast
A detected slave configuration error:
  • Slave configured but not detected
  • Slave detected but not configured
  • Slave detected and configured but not active
  • Profile is not the same as the one declared
NOTE: To access detailed information about a slave with a detected error, connect a programming tool to the slave. The module LEDs only indicate that there is a anomaly in the slave.
ASI PWR LED
This green LED provides information about the voltage on the AS-Interface bus:
ASI PWR
AS-Interface Power Supply Status
Off
Voltage level is not correct
On
Voltage level is correct
FAULT LED
This red LED provides information about the AS-Interface bus:
FAULT
AS-Interface Bus Status
Off
OK
On
Detected AS-Interface bus error:
  • No data exchange with 1 or more slaves
  • In OFFLINE Mode
  • Module is not ready for normal AS-Interface bus operation
Flashing
Detected periphery error on 1 or more slaves
NOTE: In case of simultaneous “no data exchange” and “periphery error”, the FAULT LED flashes, i.e., “periphery fault” has priority over “no data exchange”.
NOTE: A “periphery fault” is also indicated in the Module Fault tab on the module diagnostics page.