RUN
|
ERR
|
I/O
|
Status of Module
|
---|---|---|---|
Off
|
Off
|
Off
|
Under-voltage or LEDs non-functional
|
Flashing
|
Off
|
Off
|
Waiting for the module configuration download
|
Flashing
|
Flashing
|
Flashing
|
Self tests
|
Off
|
Flashing
|
Off
|
Module is not correctly configured
|
On
|
Off
|
Off
|
Normal running mode (in the Protected Mode with data exchange on the bus)
|
Off
|
On
|
Off
|
Detected internal module error
|
On
|
Off
|
On
|
Detected error in the AS-Interface application (bus or slave)
|
On
|
Flashing
|
Off
|
Communication error detected with the PLC
|
A/B
|
Slaves Displayed
|
---|---|
Off
|
Bank A (standard and extended slaves)
|
On
|
Bank B (only extended slaves)
|
Slave Address LED
|
Slave Status
|
---|---|
Off
|
Slave not configured and not detected
|
On
|
Slave active (configured, detected and activated)
|
Flashing Slow
|
Peripheral error detected on slave
|
Flashing Fast
|
A detected slave configuration error:
|
ASI PWR
|
AS-Interface Power Supply Status
|
---|---|
Off
|
Voltage level is not correct
|
On
|
Voltage level is correct
|
FAULT
|
AS-Interface Bus Status
|
---|---|
Off
|
OK
|
On
|
Detected AS-Interface bus error:
|
Flashing
|
Detected periphery error on 1 or more slaves
|