Characteristic
|
Value
|
---|---|
Maximum cycle time of bus: (2+n)*156 μs
where n = number of active slaves
|
5 ms for 31 standard or extended address setting slaves,
10 ms for 62 extended address setting slaves.
|
Maximum number of slaves on the bus
|
31 standard address setting slaves or
62 extended address setting slaves.
|
Maximum length of AS-Interface bus cables:
all branches without repeater
with two repeaters at 100 m and 200 m
|
100 meters
300 meters
|
Maximum number of I/O managed by the bus
|
Standard address setting slaves: 124 inputs +124 outputs
Extended address setting slaves: 496 inputs + 496 outputs
|
Nominal bus supply voltage
|
30 VDC
|
Characteristic
|
Value
|
---|---|
Programming the module
|
Unity Pro V4.1 or later.
NOTE: Unity Pro is the former name of Control Expert for version 13.1 or earlier. |
Supported CPU type
|
M340:
M580:
|
Response time with 31 slaves(1) for a PLC cycle time of 10 ms
|
40 ms typical / 65 ms maximum
|
Power consumption 3.3 VDC PLC
|
160 mA typical
|
Power consumption on 30 VDC AS-Interface/AS-Interface
|
27 mA typical
|
Typical Power dissipation
|
2.5 W
|
Reverse polarity protection on bus inputs
|
Yes
|
Degree of protection
|
IP20
|
Isolated voltage
|
500 VDC
|
Operating temperature
|
0 °C to 60 °C (32 °F to 140 °F)
|
Storage temperature
|
-40 °C to 85 °C (-40 °F to 185 °F)
|
AS-Interface master profile
|
M4
|
Standards and service conditions
|
|
(1) Logical response time = time between an AS-Interface input is activated on the bus, processed in the PLC application and applied to an AS-Interface output. |