Technical Characteristics
Original instructions
AS-Interface Bus
The table below gives the technical characteristics of the AS-Interface bus:
Characteristic
Value
Maximum cycle time of bus: (2+n)*156 μs
where n = number of active slaves
5 ms for 31 standard or extended address setting slaves,
10 ms for 62 extended address setting slaves.
Maximum number of slaves on the bus
31 standard address setting slaves or
62 extended address setting slaves.
Maximum length of AS-Interface bus cables:
all branches without repeater
with two repeaters at 100 m and 200 m
100 meters
300 meters
Maximum number of I/O managed by the bus
Standard address setting slaves: 124 inputs +124 outputs
Extended address setting slaves: 496 inputs + 496 outputs
Nominal bus supply voltage
30 VDC
Altitude Operating Conditions
The characteristics in the table below apply to the module BMX EIA 0100 for use at altitude up to 2000 m (6560 ft). When the modules operate above 2000 m (6560 ft), apply additional derating.
For detailed information, refer to chapter Operating and Storage Conditions.
BMX EIA 0100 Module
The table below gives the technical characteristics of the BMX EIA 0100:
Characteristic
Value
Programming the module
Unity Pro V4.1 or later.
NOTE: Unity Pro is the former name of Control Expert for version 13.1 or earlier.
Supported CPU type
M340:
  • BMX P34 1000 (requires CPU OS 2.1 or later)
  • BMX P34 2000 (requires CPU OS 2.1 or later)
  • BMX P34 20102
  • BMX P34 2020 (requires CPU OS 2.1 or later)
  • BMX P34 20302
M580:
  • BMX P58 ••••
    NOTE: When located in an X80 drop the BMX EIA 0100 requires an (e)X80 performance drop adapter module BM• CRA 31210.
Response time with 31 slaves(1) for a PLC cycle time of 10 ms
40 ms typical / 65 ms maximum
Power consumption 3.3 VDC PLC
160 mA typical
Power consumption on 30 VDC AS-Interface/AS-Interface
27 mA typical
Typical Power dissipation
2.5 W
Reverse polarity protection on bus inputs
Yes
Degree of protection
IP20
Isolated voltage
500 VDC
Operating temperature
0 °C to 60 °C (32 °F to 140 °F)
Storage temperature
-40 °C to 85 °C (-40 °F to 185 °F)
AS-Interface master profile
M4
Standards and service conditions
(1) Logical response time = time between an AS-Interface input is activated on the bus, processed in the PLC application and applied to an AS-Interface output.