Analog Input Values
Original instructions
Description
For RTD and TC sensors, the data is a multiple of 10 of the real temperature in °C or °F. The last digit represents 0.1°C or 0.1°F.
For millivoltmeter, the data ranges from 40 mV, 320 mV to 1280 mV and is also a multiple of 10 of the real measurement. The last digit represents 10 nV.
For millivoltmeter, the data range of 640 mV is a multiple of 100 of the real measurement. The last digit represents 100 nV.
RTD Ranges
The table below presents the ranges for the RTD sensors (values in brackets are in 1/10°F).
Range
Under flow
Lower scale
Upper scale
Over flow
Pt100 IEC 751-1995, JIS C1604-1997 (2/4 wires)
-1990
(-3260)
-1750
(-2830)
8250
(15170)
8490
(15600)
Pt1000 IEC 751-1995, JIS C1604-1997 (2/4 wires)
-1990
(-3260)
-1750
(-2830)
8250
(15170)
8490
(15600)
Ni100 DIN43760-1987 (2/4 wires)
-590
(-750)
-540
(-660)
1740
(3460)
1790
(3550)
Ni1000 DIN43760-1987 (2/4 wires)
-590
(-750)
-540
(-660)
1740
(3460)
1790
(3550)
Pt100 IEC 751-1995, JIS C1604-1997 (3 wires)
-1990
(-3260)
-1750
(-2830)
8250
(15170)
8490
(15600)
Pt1000 IEC 751-1995, JIS C1604-1997 (3 wires)
-1990
(-3260)
-1750
(-2830)
8250
(15170)
8490
(15600)
Ni100 DIN43760-1987 (3 wires)
-590
(-750)
-540
(-660)
1740
(3460)
1790
(3550)
Ni1000 DIN43760-1987 (3 wires)
-590
(-750)
-540
(-660)
1740
(3460)
1790
(3550)
JPt100 JIS C1604-1981, JIS C1606-1989 (2/4 wires)
-990
(-1460)
-870
(-1240)
4370
(8180)
4490
(8400)
JPt1000 JIS C1604-1981, JIS C1606-1989 (2/4 wires)
-990
(-1460)
-870
(-1240)
4370
(8180)
4490
(8400)
JPt100 JIS C1604-1981, JIS C1606-1989 (3 wires)
-990
(-1460)
-870
(-1240)
4370
(8180)
4490
(8400)
JPt1000 JIS C1604-1981, JIS C1606-1989 (3 wires)
-990
(-1460)
-870
(-1240)
4370
(8180)
4490
(8400)
Cu10 (2/4 wires)
-990
(-1460)
-910
(-1320)
2510
(4840)
2590
(4980)
Cu10 (3 wires)
-990
(-1460)
-910
(-1320)
2510
(4840)
2590
(4980)
TC Ranges
The table below presents the ranges for the TC sensors (values in brackets are in (1/10°F).
Range
Under flow
Lower scale
Upper scale
Over flow
Type J
-1980
(-3260)
-1770
(-2870)
7370
(13590)
7580
(13980)
Type K
-2680
(-4500)
-2310
(-3830)
13310
(24270)
13680
(24940)
Type E
-2690
(-4510)
-2400
(-3990)
9700
(17770)
9990
(18290)
Type T
-2690
(-4520)
-2540
(-4250)
3840
(7230)
3990
(7500)
Type S
-500
(-540)
-90
(160)
17270
(29550)
17680
(30250)
Type R
-500
(-540)
-90
(160)
17270
(29550)
17680
(30250)
Type B
1320
(2700)
1710
(3390)
17790
(32000)
18170
(32000)
Type N
-2670
(-4500)
-2320
(-3860)
12620
(23040)
12970
(23680)
Type U
-1990
(-3250)
-1810
(-2930)
5810
(10770)
5990
(11090)
Type L
-1990
(-3250)
-1740
(-2800)
8740
(16040)
8990
(16490)
Voltage Ranges
The table below presents the voltage ranges default values.
Range
Under flow
Lower scale
Upper scale
Over flow
+/- 40 mV
-4192
-4000
4000
4192
+/- 80 mV
-8384
-8000
8000
8384
+/- 160 mV
-16768
-16000
16000
16768
+/- 320 mV
-32000
-32000
32000
32000
+/- 640 mV
-6707
-6400
6400
6707
+/- 1280 mV
-13414
-12800
12800
13414
Resistance Ranges
The table below presents the resistance ranges default values.
Range
Under flow
Lower scale
Upper scale
Over flow
0-400 Ohms 2/4 wires
0
0
4000
4096
0-4000 Ohms 2/4 wires
0
0
4000
4096
0-400 Ohms 3 wires
0
0
4000
4096
0-4000 Ohms 3 wires
0
0
4000
4096