Type of inputs
|
Isolated, RTD, thermocouple and voltage inputs
|
|
Nature of inputs
|
+/- 40 mV; +/- 80 mV; +/- 160 mV; +/- 320 mV; +/- 640 mV; 1.28 V
|
|
Operating temperature
|
BMX ART 0414
BMX ART 0814
|
0...60 ºC (32...140 ºF)
|
BMX ART 0414H
BMX ART 0814H
|
-25...70 ºC (-13...158 ºF)
|
|
Number of channels
|
BMX ART 0414(H)
|
4
|
BMX ART 0814(H)
|
8
|
|
Acquisition cycle time
|
BMX ART 0414(H)
|
400 ms / 4 channels
|
BMX ART 0814(H)
|
400 ms / 8 channels
|
|
Conversion method
|
ΣΔ
|
|
Resolution
|
15-bit + sign
|
|
Isolation:
|
|
|
Maximum authorized over voltage for inputs
|
+/- 7.5 Vdc
|
|
Cold junction compensation
|
|
|
Input filter
|
Low pass filter (1st order numerical)
|
|
Rejection in differential mode (50/60 Hz)
|
Typical 60 dB
|
|
Common mode rejection (50/60 Hz)
|
Typical 120 dB
|
|
BMX ART 0414(H)
|
||
Power consumption (3.3 V)
|
Typical
|
0.32 W
|
Maximum
|
0.48 W
|
|
Power consumption (24 V)
|
Typical
|
0.47 W
|
Maximum
|
1.20 W
|
|
BMX ART 0814(H)
|
||
Power consumption (3.3 V)
|
Typical
|
0.32 W
|
Maximum
|
0.48 W
|
|
Power consumption (24 V)
|
Typical
|
1.00 W
|
Maximum
|
1.65 W
|
Voltage range:
|
+/- 40 mV; +/- 80 mV; +/- 160 mV; +/- 320 mV; +/- 640 mV; 1.28 V
|
Input impedance:
|
Typical 10 MOhms
|
Maximum converted value:
|
+/- 102.4%
|
Maximum resolution:
|
2.4 μV in the range +/- 40 mV
|
Measurement error for standard module:
|
|
|
0.05% of FS (1)
|
|
0.15% of FS (1)
|
Measurement error for Hardened module:
|
|
|
0.05% of FS (1)
|
|
0.20% of FS (1)
|
Temperature drift:
|
|
30 ppm/°C
|
|
Legend:
|
|
(1) FS: Full Scale
|
RTD
|
Pt100
|
Pt1000
|
Ni100
|
Ni1000
|
Cu10
|
CU50
|
CU100
|
---|---|---|---|---|---|---|---|
Measurement range
|
According to IEC
-175... +825°C
(-347...+1517°F)
According to US/JIS:
-87 +437°C
(-125...+819°F)
|
-54...+174°C
(-65...+345°F)
|
-91...+251°C (-132...+484°F)
|
-200...+200°C
(-328...+392)
|
|||
Resolution
|
0.1°C (0.2°F)
|
||||||
Detection type
|
Open circuit (detection on each channel)
|
||||||
Error at 25 °C (77 °F) (1)
|
+/- 2.1 °C (+/- 3.8°F)
|
+/- 2.1 °C
(+/- 3.8°F)
|
+/- 0.7°C
(+/- 1.3°F)
|
+/- 4 °C
(+/- 7.2°F)
|
+/- 2.1°C
(+/- 3.8°F)
|
||
Maximum error for standard modules in the temperature range 0...60° C (32...140 °F) (2)
|
+/- 3 °C (+/- 5.4°F)
|
+/- 3 °C (+/- 5.4°F)
|
+/- 0.7°C (+/- 1.3°F)
|
+/- 4 °C
(+/- 7.2°F)
|
+/- 3°C
(+/- 5.4°F)
|
||
Maximum error for hardened modules in the temperature range -25...70 °C (-13...140 °F) (2)
|
+/- 3 °C (+/- 5.4°F)
|
+/- 3.5°C (+/- 6.3°F)
|
+/- 1.15°C (+/- 2.1°F)
|
+/- 4.5°C (+/- 8.1°F)
|
+/- 3.5°C
(+/- 6.3°F)
|
||
Maximum wiring resistance:
|
|||||||
|
50 Ω
|
500 Ω
|
50 Ω
|
500 Ω
|
50 Ω
|
50 Ω
|
|
|
20 Ω
|
200 Ω
|
20 Ω
|
200 Ω
|
20 Ω
|
20 Ω
|
|
Temperature drift:
|
|||||||
30 ppm/°C
|
|||||||
Legend
|
|||||||
(1) errors caused by the wiring, +/- 1°C (0.2°F) in the range -100...+200°C (-148...+392°F) for Pt100
(2) See detailed errors at temperature point.
|
Thermocouples
|
B
|
E
|
J
|
K
|
L
|
---|---|---|---|---|---|
Measurement range
|
+171... +1,779°C (340... 3234°F)
|
-240... +970°C (-400... 1778°F)
|
-177... +737°C (-287... 1359°F)
|
-231... +1,331°C (-384... 2428°F)
|
-174... +874°C (-281... 1605°F)
|
|
|||||
Thermocouples
|
N
|
R
|
S
|
T
|
U
|
Measurement range
|
-232 +1,262°C (-386... 2304°F)
|
-9... +1,727°C (16... 3234°F)
|
-9... +1,727°C (-16... 141°F)
|
-254... +384°C (-425... 723°F)
|
-181... +581°C (-294... 1078°F)
|
|
|||||
Resolution
|
0.1°C (0.2°F)
|
||||
Detection type
|
Open circuit (detection on each channel)
|
||||
Error at 25°C
|
+/- 3.2°C for J, L, R, S and U types (see Thermocouple Ranges for detailed errors at temperature point for each type); +/- 3.7°C for B, E, K, N and T types
|
||||
Maximum error for standard modules in the temperature range 0...60°C (32...140°F) (2)
|
+/- 4.5°C (+/-8.1°F) for types: J, L, R, S and U; +/- 5°C (+/-9°F) for types: B, E, K, N and T (using the TELEFAST accessory with its internal cold junction compensation).
|
||||
Maximum error for hardened modules in the temperature range -25...70 °C (-13...140 °F) (2)
|
+/- 5.5°C (+/-9°F) for types: J, L, R, S and U; +/- 6°C (+/-10.8°F) for types: B, E, K, N and T (using the TELEFAST accessory with its internal cold junction compensation).
|
||||
Temperature drift
|
30 ppm/°C
|
Range
|
400 Ω; 4000 Ω
|
Type measurement
|
2, 3, 4 wires
|
Maximum resolution
|
12.5 mΩ in the range 400 Ω
125 mΩ in the range 4000 Ω
|
Measurement error for standard module:
|
|
|
0.12% of FS (1)
|
|
0.2% of FS (1)
|
Measurement error for ruggedized module:
|
|
|
0.12% of FS (1)
|
|
0.3% of FS (1)
|
Temperature drift
|
25 ppm/°C
|
Legend:
|
|
(1) FS: Full Scale
|