Measurements provided to the application are usable directly. You may choose between:
-
using standardized display 0...10000 (or +/- 10000 for range +/‐ 10 V),
-
customizing the display format by providing desired minimum and maximum values.
Values are displayed in standardized measuring units (in percent format, with two decimal spaces, also symbolized as °/

):
Type of Range
|
Display
|
unipolar range
|
from 0 to 10000 (0 °/  to +10000 °/  )
|
bipolar range
|
from -10000 to 10000 (-10.000 °/  to +10000 °/  )
|
-
the lower threshold corresponding to the minimum value for the range: 0°/

(or ‐10000°/

),
-
the upper threshold corresponding to the maximum value for the range (+10000°/

).
These lower and upper thresholds are integers between -30000 and +30000.
Example:
Imagine a conditioner providing pressure data on a 4-20 mA loop, with 4 mA corresponding to 3200 mB, and 20 mA corresponding to 9600 mB. You have the option of choosing the User format, by setting the following lower and upper thresholds:
3200°/

for 3200 mB as the lower threshold,
9600°/

for 9600 mB as the upper threshold.
Values transmitted to the program vary between 3200 (= 4 mA) and 9600 (= 20 mA).
Therefore, matches are as follows:
Value transmitted to program
|
Current
|
Pressure
|
3200
|
4 mA
|
3200 mB
|
current value
|
between 4 and 20 mA
|
current value
|
9600
|
20 mA
|
9600 mB
|