Measurement Display
(Original Document)
Introduction
Measurements provided to the application are usable directly. You may choose between:
Standardized Display
Values are displayed in standardized measuring units (in percent format, with two decimal spaces, also symbolized as °/):
Type of Range
Display
unipolar range
from 0 to 10000 (0 °/ to +10000 °/)
bipolar range
from -10000 to 10000 (-10.000 °/ to +10000 °/)
User-Specified Display
You have the option of defining the range of values within which measurements are expressed, by selecting:
These lower and upper thresholds are integers between -30000 and +30000.
Example:
Imagine a conditioner providing pressure data on a 4-20 mA loop, with 4 mA corresponding to 3200 mB, and 20 mA corresponding to 9600  mB. You have the option of choosing the User format, by setting the following lower and upper thresholds:
3200°/ for 3200 mB as the lower threshold,
9600°/ for 9600 mB as the upper threshold.
Values transmitted to the program vary between 3200 (= 4 mA) and 9600 (= 20 mA).
Therefore, matches are as follows:
Value transmitted to program
Current
Pressure
3200
4 mA
3200 mB
current value
between 4 and 20 mA
current value
9600
20 mA
9600 mB