Measurement Filtering
(Original Document)
Introduction
The type of filtering performed by the system is called "first order filtering." The filtering coefficient is editable from a programming console or through the program.
Mathematical Formula
The applicable mathematical formula is as follows:
where :
= filter efficiency,
Mesf(n) = filtered measurement at time n,
Mesf(n-1) = filtered measurement at time n-1,
Valb(n) = raw value at time n.
User configures the filtering value from 7 possibilities. This value may be changed even when application is in RUN mode.
NOTE: Filtering is disabled in Fast Cycle mode.
Values for the TSX AEY 810 Module
Filtering values are as follows:
Desired Efficiency
Required Value
corresponding
Filter Response Time at 63 %
Cut-off Frequency (in Hz)
No filtering
0
0
0
0
Low filtering
1
2
0,750
0,875
104.3 ms
224.7 ms
1,526
0,708
Medium filtering
3
4
0,937
0,969
464.8 ms
944.9 ms
0,342
0,168
High filtering
5
6
0,984
0,992
1.905 ms
3.825 ms
0,084
0,042