Type of outputs
|
Common pulse outputs
|
Nature of outputs
|
Voltage / Current
|
Number of channels
|
8
|
Output refresh time
|
5 ms
|
Power supply for outputs
|
provided by the PLC or external 24 V supply
|
Types of protection
|
Short circuits and overloads
|
Insulation:
|
Common pulse
1000 V rms
1000 V rms
|
Isolation resistance under 500VDC between channel and ground
|
> 10 mOhms
|
Diaphony between channels
|
-80 dB
|
Monotonicity
|
Yes
|
Non linearity
|
<= 1 LSB
|
RC network ground connection
|
R = 50 MOhms, C = 4.7 nF
|
Dissipated power:
|
5 W
6.1 W
|
Voltage output dynamic
|
+/- 10.5 V
|
Full scale (FS)
|
10 V
|
Max voltage without damaging the voltage outputs
|
+/- 30 V
|
Load impedance
|
1 KOhm minimum
|
Capacitative load
|
< 100 nF
|
Maximum resolution:
|
1.28 mV to +/- 10 V
|
Measuring error:
|
+/- 0.14 % of FS
+/- 0.28 % of FS (26 ppm/°C)
|
Current output dynamic
|
21 mA
|
Full scale (FS)
|
20 mA
|
Max voltage without damaging the voltage outputs
|
+/- 30 V
|
Load impedance
|
600 Ohms maximum
|
Inductance load
|
< 0.3 mH
|
Maximum resolution:
|
0.00256 mA
|
Measuring error:
|
+/- 0.21 % of FS (1)
+/- 0.52 % of FS (64 ppm/°C)
|
Maximum leakage current
|
0.033 mA
|
Legend
|
|
(1) Precision calculated in a ventilated cabinet (in a non-ventilated cabinet, the precision is: 0.32 % of FS.
|
Characteristics
|
24 V +/- 5 %
ripple of 1 V maximum
|
Cable
|
Shielded cable
|
Power consumption:
|
300 mA
455 mA
|
Connection
|
Removable screw terminal block
|