Type of inputs
|
Isolated inputs, low and high level, thermocouples and thermoprobes
|
Type of inputs
|
Multi-range
|
Number of channels
|
4
|
Acquisition cycle time
|
550 ms for the 4 channels
|
Analog / Digital converter
|
16 bits (0..65535 pulses)
|
Digital filtering
|
1st order (Time constant = 0 to 68.5 s)
|
Insulation:
|
2830 V rms
1780 V rms
1780 V rms
|
Isolation resistance under 500VDC between channel and ground
|
> 10 mOhms
|
Maximum over-voltage in differential mode authorized for inputs
|
+/- 30 VDC (switched on, without 250 Ω external shunt)
+/-15 VDC (switched off, without 250 Ω external shunt)
|
Maximum over-voltage authorized for inputs
|
+/-25 mA (switched on/off, with 250 Ω external shunt)
|
Linearization
|
Automatic
|
Common mode voltage acceptable in operation:
|
200 VDC or 415 VAC
100 VDC or 240 VAC
|
Cold junction compensation
|
Automatic
Between -5 and +85°C
|
Thermoprobe current
|
2.5 mA DC at 100 Ω
0.559 mA DC at 1000 Ω
|
Maximum power dissipation
|
4.7 W
|
PLC Standards
|
IEC1131, IEC801, IEC68, UL508, UL94
|
Sensor Standards
|
IEC584, IEC751, DIN43760, DIN43710, NFC42-330
|
Measurement range
|
Input impedance)
|
Full scale (FS)
|
Maximum error at 25°C (2)
|
Maximum error from 0 to 60°C (2)
|
---|---|---|---|---|
+/- 10 V
|
10 MΩ
|
10 V
|
0.27 % of FS
|
0.50 % of FS
|
0..10 V
|
10 MΩ
|
10 V
|
0.16 % of FS
|
0.39 % of FS
|
+/- 5 V
|
10 MΩ
|
5 V
|
0.27 % of FS
|
0.50 % of FS
|
0..5 V (1)
|
10 MΩ
|
5 V
|
0.22 % of FS
|
0.45 % of FS
|
1..5 V (1)
|
10 MΩ
|
5 V
|
0.27 % of FS
|
0.56 % of FS
|
0..20 mA (1)
|
250 Ω
|
20 mA
|
0.36 % of FS
|
0.69 % of FS
|
4..20 mA (1)
|
250 Ω
|
20 mA
|
0.45 % of FS
|
0.86 % of FS
|
-13.+63 mV
|
10 MΩ
|
63 mV
|
0.19 % of FS
|
0.44 % of FS
|
0..400 Ω
|
400 Ω
|
0.13 % of FS
|
0.27 % of FS
|
|
0..3850 Ω
|
3850 Ω
|
0.22 % of FS
|
0.48 % of FS
|
|
Legend:
|
||||
(1)
|
The 0..5 V and 0..20 mA or 1..5 V and 4..20 mA ranges are configured in the same manner, with the only difference being whether or not a 250 Ω shunt is installed.
|
|||
(2)
|
For electric ranges, the precision values encompass the entire input dynamic.
|
Measurement range
|
Maximum error at 25°C
|
Maximum error from 0 to 60°C
|
---|---|---|
Pt100 according to IEC
|
1.2°C
|
2.4°C
|
Pt1000 according to IEC
|
2.5°C
|
5.0°C
|
Ni1000 according to DIN
|
1.1°C
|
2.0°C
|
Measurement range
|
Maximum error at 25°C
|
Maximum error from 0 to 60°C
|
||
---|---|---|---|---|
IC
|
EC
|
IC
|
EC
|
|
B
|
3.5°C
|
/
|
8.1°C
|
/
|
E
|
6.1°C
|
1.5°C
|
8.1°C
|
3.2°C
|
J
|
7.3°C
|
1.9°C
|
9.5°C
|
4.0°C
|
K
|
7.8°C
|
2.3°C
|
10.5°C
|
4.7°C
|
L
|
7.5°C
|
2.0°C
|
9.8°C
|
4.2°C
|
N
|
6.0°C
|
2.0°C
|
8.7°C
|
4.3°C
|
R
|
6.0°C
|
3.2°C
|
11.0°C
|
7.7°C
|
S
|
6.6°C
|
3.4°C
|
12.0°C
|
8.5°C
|
T
|
6.6°C
|
1.5°C
|
8.8°C
|
3.3°C
|
U
|
5.4°C
|
1.5°C
|
7.3°C
|
3.1°C
|
Legend:
|
||||
IC
|
With internal cold junction compensation:
|
|||
EC
|
With internal cold junction compensation: Values in this column were obtained from across channel 0 using a class A Pt100 probe.
|