Characteristics of the primary block
|
Nominal voltage
|
125 Vdc
|
|
Voltage range
|
100-150 Vdc
|
||
Power
|
45 W
|
||
Nominal current consumption
|
0.36 A at 125 Vdc
|
||
Initial power-up at 25 °C(1)
|
InRush current I
|
≤ 30 A at 125 Vdc
|
|
I2t
at locking
|
≤ 2 A2s at 125 Vdc
|
||
It
at locking
|
≤ 0.05 As at 125 Vdc
|
||
Acceptable duration of power interruptions
|
≤ 10 ms
|
||
Built-in over-current protection
|
By internal, inaccessible fuse
|
||
Characteristics of the secondary block
|
Total useful power
|
36 W
|
|
Maximum useful power at the two outputs, 3V3_BAC and 24V_BAC
|
31.2 W
|
||
3V3_BAC output
|
Nominal voltage
|
3.3 Vdc
|
|
Nominal current
|
4.5 A
|
||
Power (typical)
|
15 W
|
||
24V_BAC output
|
Nominal voltage
|
24 Vdc
|
|
Nominal current
|
1.3 A
|
||
Power (typical)
|
31.2 W
|
||
24V_SENSORS output
|
Nominal voltage
|
24 Vdc
|
|
Nominal current
|
0.9 A
|
||
Power (typical)
|
21.6 W
|
||
3V3_BAC, 24V_BAC and 24V_SENSORS output protection
|
Against overload, short circuits and over-voltage
|
||
Maximum Dissipated Power
|
8.5 W
|
||
Characteristics of the auxiliary functions
|
Alarm relay
|
Normally open dry contacts
|
|
Display
|
Front panel LED
|
||
Back-up battery
|
No
|
||
Isolation
|
Dielectric resistance
at 50 Hz-1mn
|
Primary/secondary (24V_BAC/3V3_BAC)
|
3,000 Vrms
|
Primary/secondary (24V_SENSORS)
|
3,000 Vrms
|
||
Primary/ground
|
2,000 Vrms
|
||
24V_SENSORS/ground output
|
500 Vrms
|
||
Insulation resistance
|
Primary/secondary
|
≥ 100 MΩ
|
|
Primary/ground
|
≥ 100 MΩ
|
||
Operating temperature
|
-25...70 °C (-13...158 °F)
|
||
(1) These values are to be taken into account for the start-up of several devices simultaneously or for establishing the size of the protection devices. |