Characteristics of the BMXCPS3540T Power Supply Module
Original instructions
Introduction
The BMXCPS3540T module is a direct current (125 Vdc) power supply module.
Altitude Operating Conditions
The characteristics in the table below apply to the BMXCPS3540T power supply module for use at altitude up to 2000 m (6560 ft). When the power supply module operate above 2000 m (6560 ft), apply additional derating.
For detailed information, refer to chapter Operating and Storage Conditions.
Characteristics
Characteristics of the primary block
Nominal voltage
125 Vdc
Voltage range
100-150 Vdc
Power
45 W
Nominal current consumption
0.36 A at 125 Vdc
Initial power-up at 25 °C(1)
InRush current I
≤ 30 A at 125 Vdc
I2t
at locking
≤ 2 A2s at 125 Vdc
It
at locking
≤ 0.05 As at 125 Vdc
Acceptable duration of power interruptions
≤ 10 ms
Built-in over-current protection
By internal, inaccessible fuse
Characteristics of the secondary block
Total useful power
36 W
Maximum useful power at the two outputs, 3V3_BAC and 24V_BAC
31.2 W
3V3_BAC output
Nominal voltage
3.3 Vdc
Nominal current
4.5 A
Power (typical)
15 W
24V_BAC output
Nominal voltage
24 Vdc
Nominal current
1.3 A
Power (typical)
31.2 W
24V_SENSORS output
Nominal voltage
24 Vdc
Nominal current
0.9 A
Power (typical)
21.6 W
3V3_BAC, 24V_BAC and 24V_SENSORS output protection
Against overload, short circuits and over-voltage
Maximum Dissipated Power
8.5 W
Characteristics of the auxiliary functions
Alarm relay
Normally open dry contacts
Display
Front panel LED
Back-up battery
No
Isolation
Dielectric resistance
at 50 Hz-1mn
Primary/secondary (24V_BAC/3V3_BAC)
3,000 Vrms
Primary/secondary (24V_SENSORS)
3,000 Vrms
Primary/ground
2,000 Vrms
24V_SENSORS/ground output
500 Vrms
Insulation resistance
Primary/secondary
≥ 100 MΩ
Primary/ground
≥ 100 MΩ
Operating temperature
-25...70 °C (-13...158 °F)
(1) These values are to be taken into account for the start-up of several devices simultaneously or for establishing the size of the protection devices.
NOTE: In order to restart the power supply after a detected output overload, short circuit, or over-voltage condition on the 24V_BAC, you must switch the primary power line to the off state, wait 1 minute, and then switch the primary power line back to the on state.