Characteristics of the BMXCPS2010 Power Supply Module
Original instructions
Introduction
The BMXCPS2010 module is a direct current (24 Vdc) power supply module.
Altitude Operating Conditions
The characteristics in the table below apply to the BMXCPS2010 power supply module for use at altitude up to 2000 m (6560 ft). When the power supply module operate above 2000 m (6560 ft), apply additional derating.
For detailed information, refer to chapter Operating and Storage Conditions.
Characteristics
Characteristics of the primary block
Nominal voltage
24 Vdc
Voltage range
19.2 - 31.2 Vdc
Nominal current consumption
1 A at 24 Vdc
Initial power-up at 25 °C(1)
InRush current I
30 A at 24 Vdc
I2t
at locking
≤ 0.6 A2s at 24 Vdc
It
at locking
≤ 0.15 As at 24 Vdc
Acceptable duration of power interruptions
≤ 1 ms
Built-in over-current protection
By internal, inaccessible fuse
Characteristics of the secondary block
Total usable power
17 W
3V3_BAC output
Nominal voltage
3.3 Vdc
Nominal current
2.5 A
Power (typical)
8.3 W
24V_BAC output
Nominal voltage
24 Vdc
Nominal current
0.7 A
Power (typical)
16.5 W
3V3_BAC and 24V_BAC output protection
Against overload, short circuits and over-voltage
Maximum Dissipated Power
8.5 W
Characteristics of the auxiliary functions
Alarm relay
Normally open dry contacts
Display
Front panel LED
Back-up battery
No
Isolation
Dielectric resistance
at 50 Hz-1mn
Primary/secondary (24V_BAC/3V3_BAC)
1,500 Vrms
Primary/ground
1,500 Vrms
Insulation resistance
Primary/secondary
≥ 10 MΩ
Primary/ground
≥ 10 MΩ
Operating temperature
0...60 °C (32...140 °F)
(1) These values are to be taken into account for the start-up of several devices simultaneously or for establishing the size of the protection devices.