Two BMENOS0300 Modules in RIO Drop of Standalone PAC Supporting RIO Sub-Ring and DIO Ring
Original instructions
RIO Sub-Ring and DIO Ring
In this topology, two BMENOS0300 network option switches are used in place of external dual ring switches (DRSs) to reduce cost. The two BMENOS0300 network option switch modules reside in an RIO drop. The ports of these modules are used as follows:
1 
Standalone PAC on local rack
2 
Ethernet main RIO ring
3 
(e)X80 RIO drop
4 
Ethernet RIO sub-ring
5 
Ethernet DIO ring
6 
Distributed equipment
7 
Ethernet daisy chain
8 
Engineering tool resident on PC
NOTE:
  • To achieve desired RSTP-based network response time targets, the longest path that an Ethernet RIO packet would have to travel in the case of a cable break is 32 switched devices, including:
    • the CPU
    • the remote adapter (BMECRA312•0)
    • the embedded switch in the Ethernet rack on which the BMENOS0300 modules are installed
    • the BMENOS0300 module
  • When you set the BMENOS0300 network rotary switch to RIO Ring, configure the RSTP bridge identifier priority settings of other devices in the RIO sub-ring to values greater than 0. Refer to the topic Device Rotary Switch Positions for information about the effects of selecting RIO Ring.
  • To achieve acceptable recovery times, limit the DIO design to a single DIO main ring without sub-rings.
  • When you set the BMENOS0300 network rotary switch to DIO Ring, configure a distributed equipment Ethernet device to be the RSTP root bridge. Refer to the topic Device Rotary Switch Positions for information about the effects of selecting DIO Ring.
  • RSTP limits the size of the DIO ring to a maximum of 40 switched devices, including the BMENOS0300 module.