Functions and Protocols

The BMENOR2200H module provides in-rack support for these functions and protocols in an M580 architecture:

RTU protocols

built-in RTU protocols for serial or Ethernet communications

IEC60870-5-101 (server or client)

IEC60870-5-104 (server or client)

DNP3 serial (server or client)

DNP3 NET (server or client)

Modbus TCP (server or client)

NOTE: The number of communication connections servers affects the module performance (web page access, module start-up and data exchange through the backplane).

Main RTU protocol features

time synchronization through a protocol facility or SNTP

data synchronization on demand of the SCADA

event management with time stamping (Sequence of Events, SoE)

event queue stored in RAM memory (up to 150,000 events)

events data backfill to SCADA application via protocol facility

event routing

report by exception data exchanges

unsolicited messaging data exchanges

DNP3 secure authentication SAv2 and SAv5 with pre-shared key

protocol configuration in the DTM

Other built-in functionality

web server for security set-up and remote diagnostic