Functions and Protocols
The BMENOR2200H module provides in-rack support for these functions and protocols
in an M580 architecture:
RTU protocols |
built-in RTU protocols for serial or Ethernet communications |
IEC60870-5-101 (server or client) |
|
IEC60870-5-104 (server or client) |
|
DNP3 serial (server or client) |
|
DNP3 NET (server or client) |
|
Modbus TCP (server or client) |
|
NOTE: The number of communication connections servers affects
the module performance (web page access, module start-up and data
exchange through the backplane).
|
|
Main RTU protocol features |
|
data synchronization on demand of the SCADA |
|
event management with time stamping (Sequence of Events, SoE) |
|
event queue stored in RAM memory (up to 150,000 events) |
|
events data backfill to SCADA application via protocol facility |
|
report by exception data exchanges |
|
unsolicited messaging data exchanges |
|
DNP3 secure authentication SAv2 and SAv5 with pre-shared key |
|
protocol configuration in the DTM |
|
Other built-in functionality |
web server for security set-up and remote diagnostic |