Step
|
Action
|
---|---|
1
|
When using an application in the PCMCIA:
|
2
|
Power on the Standby CPU.
NOTE: The CPU must be in the No Conf state. |
3
|
Reconnect all the communication cables (CRP module, Ethernet cables, …) except the HSBY Link fiber optic cable.
|
4
|
At last, connect the HSBY Link fiber optic cable.
|
5
|
Check that the application program is automatically transferred to the Standby CPU. If not, perform the transfer with the keyboard.
NOTE: Verify that the Modbus or Modbus Plus address is the same as the address noted when preparing the Hot Standby system for update. |
6
|
Put the CPU in RUN mode.
Verify that the Primary CPU is in RUN Primary mode, and the Standby CPU is in RUN Standby mode.
|
7
|
Perform a switchover by stopping the Primary CPU with the keyboard.
NOTE: Verify that the Standby CPU becomes the Primary CPU (check the LCD screen). |