Quantum Modules Version, Firmware Files, and Connection
 
List of Modules, Connection, and Software for Download
The following table describes the connection and software used to download firmware and OS files in a Quantum PAC:
Module reference
Module type
Connection
Download software
140 CPU 311 10
CPU
Modbus or Modbus Plus
OS Loader
140 CPU 434 12•
140 CPU 534 14•
140 CPU 651 50
CPU with embedded Ethernet coprocessor
2 operations:
  1. Ethernet
  2. Modbus or Modbus Plus
OS Loader
140 CPU 651 60
140 CPU 652 60
140 CPU 670 60
CPU with embedded Hot Standby coprocessor
140 CPU 671 60
140 CPU 672 60
140 CPU 672 61
140 CPU 678 61
140 NOC 78• 00
Ethernet communication module
Ethernet
OS Loader
140 NOE 771 01
140 NOE 771 11
140 CRP 312 00
Ethernet RIO communication head module
Ethernet
OS Loader
140 CRA 312 00
Ethernet RIO communication adapter module
Ethernet
Unity Loader
BME CRA 312 10
BMX CRA 312 •0
140 CRP 93• 00
S908 RIO communication head and adapter module
Modbus or Modbus Plus
OS Loader
140 CRA 93• 00
NOTE: Refer to compatibility rules document in Unity Pro online help or in the release notes for more information on versions compatibility.
NOTE: When Modbus and Modbus Plus connections are available, choosing Modbus Plus connection reduces the update duration thanks to higher transfer rates.
CPU List and Files
The following table shows the Quantum CPU that can be updated:
CPU reference
140 CPU 311 10
140 CPU 434 12U
140 CPU 534 14U
Binary file name:
File type
File name structure
CPU firmware
140CPUXXXXX_Vyyy.bin XXXX: CPU reference. yyy: Firmware version.
CPU with Ethernet Coprocessor List and Files
The following table shows the Quantum CPU with Ethernet coprocessor that can be updated:
CPU reference
140 CPU 651 50
140 CPU 651 60
140 CPU 652 60
NOTE: The firmware version is displayed in the Ethernet module webpages.
Binary files name:
File type
File name structure
Coprocessor firmware
140CPUXXXXX_Copro_Exec_Vyyy.bin XXXX: CPU reference. yyy: Firmware version.
CPU firmware
140CPUXXXXX_Vyyy.bin XXXX: CPU reference. yyy: Firmware version.
Hot Standby CPU List and Files
The following table shows the Quantum Hot Standby CPU that can be updated:
CPU reference
140 CPU 671 60
140 CPU 672 60
140 CPU 672 61
140 CPU 678 61
NOTE: Hot Standby CPU have a Hot Standby coprocessor.
Binary file name:
File type
File name structure
Coprocessor firmware
140CPUXXXXX_HsbyCopro_Vyyy.bin XXXX: CPU reference. yyy: Firmware version.
CPU firmware
140CPUXXXXX_Vyyy.bin XXXX: CPU reference. yyy: Firmware version.
Ethernet Communication Module List and Files
The following table shows the communication modules that can be updated:
Module reference
140 NOC 78• ••
140 NOE 771 01
140 NOE 771 11
140 NOC 78• •• binary file name:
File type
File name structure
Module firmware
140NOC78x00_Exec_Vyyy.bin yyy: Firmware version.
140 NOE 771 01 binary files name:
File type
File name structure
140 NOE 771 01
Kernel version ≥ V2.0
Exec version ≥ V3.10
140NOE77101_Exec_Vyy.bin yy: Firmware version.
140 NOE 771 11 binary file is different for RoHS and non-RoHS modules.
Module PV
RoHS Compliant
File name structure
PV ≤ 09
Non-RoHS
NOE7711XW.bin
PV ≥ 10
RoHS
NOE7711XW.bin
Ethernet RIO Communication Head and Adapter Module List and Files
The following table shows the Ethernet RIO communication head and adapter module that can be updated:
Module reference
140 CRP 312 00
140 CRA 312 00
BME CRA 312 10
BMX CRA 312 •0
140 CRP 312 00 binary file name:
File type
File name structure
Module firmware
140CRP31200_Vyyy.bin yyy: Firmware version.
140 CRA 312 00 binary file name:
File type
File name structure
Module firmware
140CRA31200_Vyyy.ldx yyy: Firmware version.
BME CRA 312 10 binary file name:
File type
File name structure
Module firmware
BMECRA31210_Vyyy.ldx yyy: Firmware version.
BMX CRA 312 •0 binary file name:
File type
File name structure
Module firmware
BMXCRA31200 Vyyy.ldx or BMXCRA31210 Vyyy.ldx yyy: Firmware version.
S908 RIO Communication Head and Adapter Module List and Files
The following table shows the S908 RIO communication head and adapter module that can be updated:
Module reference
140 CRP 93• 00
140 CRA 93• 00
The binary file is different for RoHS and non-RoHS modules.
Non-RoHS module binary file name:
Module reference and PV
File name structure
140 CRP 93• 00
PV < 08
QCRPVyyy.bin yyy: Firmware version.
140 CRA 93• 00
PV < 09
QCRAVyyy.bin yyy: Firmware version.
RoHS module binary file name:
Module reference and PV
File name structure
140 CRP 93• 00
PV ≥ 08
RQCRPVyyy.bin yyy: Firmware version.
140 CRA 93• 00
PV ≥ 09
RQCRAVyyy.bin or 140CRA93x00_SVyyy.bin yyy: Firmware version.