IEC 60870-5-104 Client RTU Protocol Parameters
Original instructions
Introduction
Select IEC101-104 as Protocol, Master as Mode, and TCP-IP as Network Type.
Channel Parameters
Click Setup → IEC-104 Client → Channel → Parameters:
Parameter
Value scope
Default value
Description
T1 Ack Period (ms)
0...4294967295
15000
specifies the waiting time for ACK to a transmitted APDU
T2 S Frame Period (ms)
0...4294967295
10000
specifies the waiting time before transmitting the supervisory APDU ACK
T3 Test Period (ms)
0...4294967295
20000
specifies the idle time before transmitting the TEST APDU
K Value
1...12
12
indicates the maximum transmitted APDUs that are not acknowledged
W Value
0...32767
8
indicates the maximum received APDUs that are not acknowledged
Session Count
1...32
1
indicates the maximum number of sessions on the channel
NOTE: Limitations: T2 S Frame Period < T1 Ack Period and W Value < 2/3 K Value.
Configure the module’s advanced parameters:
Parameter
Value scope
Default value
Description
First Char Wait (ms)
0...65535
0
indicates the minimum time between reception and transmission
Rx Buffer Size
0...256
256
indicates the received buffer size of serial port
Offline Poll Period (ms)
0...4294967295
10000
specifies the period an offline attempts to re-establish communication
Incremental Timeout (ms)
0...4294967295
30000
indicates the incremental application layer time-out
Max Queue Size
0...65535
0
indicates the maximum request message number with specific Application Specific Data Unit type in the transmission queue
Session Parameters
Click Setup → IEC-104 Client → Channel → Session0 → Parameters:
Parameter
Value scope
Default value
Description
IP Address
255.255.255.255
192.168.0.1
indicates the IP address of remote device
Port
0...65535
2404
indicates the TCP port of remote device
Sector Count
1...5
1
indicates the sectors for this slave
COT Size
2
2
indicates octets of COT
Configure the module with advanced parameters:
Parameter
Value scope
Default value
Description
Originator Address for COT
0...255
1
specifies the originator address for COT, if the COT length is equal to 2
Default Response Timeout (ms)
0...4294967295
3000
indicates the default time-out for confirmation of request
Sector Parameters
Click Setup → IEC-104 Client → Channel → Session0 → Sector0 → Parameters:
Parameter
Value scope
Default value
Description
Common ASDU Address
1...65535
3
indicates the common address of ASDU, 65535 is broadcast address.
Configure the module with advanced parameters:
Parameter
Value scope
Default value
Description
M_EI_NA GI
check box
checked
specifies if the general interrogation is performed after receiving the M_EI_NA EOI message
M_EI_NA Time sync
check box
checked
specifies if the clock synchronization is performed after receiving the M_EI_NA EOI message
M_EI_NA CI
check box
unchecked
specifies if the counter interrogation is performed after receiving M_EI_NA EOI message
Online GI
check box
checked
specifies if the general interrogation is performed whenever the M_EI_NA EOI message is received
Online Time Sync
check box
checked
specifies if the clock synchronization is performed whenever the M_EI_NA EOI message is received
Online CI
check box
unchecked
specifies if the counter interrogation is performed whenever the M_EI_NA EOI message is received
ACTTERM with CSE Setpoint
check box
unchecked
specifies if ACTTERM is expected from slave upon completion of set point commands
ACTTERM with Command
check box
unchecked
specifies if ACTTERM is expected from slave upon completion of commands other than set point commands
Command with Time Tag
check box
unchecked
specifies if the control command follows the time tag