Email Configuration
Original instructions
Configuration Tab
Email configuration screen:
This table describes the parameters on the Configuration tab:
Parameter
Description
SendSMS
Check this box to indicate that the service can be configured to send an SMS message.
Identifier*
The email address of the message sender
Trigger*
The event that triggers the email
Type
NY: (notify): triggered by a bit status change or word value change
RE: (rising edge): triggered by a bit's rising edge or an increasing word value
FE: (falling edge): triggered by a bit's falling edge or a decreasing word value
BQ: (bad quality): triggered when the trigger status is of poor quality
Destination*
Email address(es) of the receiver(s) of the message
Subject
A brief summary of the message's contents
Contents
Type the content of the message in this area.
Source
Select the source from which the attached file comes.
Path
Specify the path of the file.
*These parameters are required to record and save an email.
Dynamic Data
The email service enables you to include dynamic data in the body of the email. You can include dynamic data manually or automatically:
Configuring European SMS Format
Before sending an SMS, you must configure the parameters from the Modem GSM window, as shown below:
The Modem GSM parameter settings available:
Parameter
Value Scope
Default Value
Description
Init AT CMD
ATE0Q0S=1&D0&S0&C0
A custom AT command is specified by user. This command initializes the modem.
PIN Code
4-8 digits
0000
PIN code for the SIM card
SMS Service Center
phone number whose length depends on service supplier
The number of the SMS service center.
SMS Type
NOTE: This parameter is supported from firmware V1.6.
PDU_7bits/ PDU_8bits
PDU_7bits
Specifies how the SMS message will be encoded and sent:
  • If encoded as 7bits, the message will be sent as a text message.
  • If encoded as 8bits, the message will be sent as a data message.
NOTE: This parameter is supported on most mobile telephones.