The following standalone CPUs with Ethernet I/O scanner service (both RIO and DIO scanner service) can be used in an open Ethernet network:
Each RIO drop contains one of the following adapter modules to be connected in an open Ethernet network:
-
BMXCRA31210(C)
-
BMECRA31210(C)
The service port bandwidth of an M580 CPU is limited to 100 Mbit/s whereas the service port bandwidth of a BM•CRA31210 module is capped to 5 Mbit/s.
Factors typically affecting network bandwidth at the service ports of the modules are:
-
Type of I/O, expert or communication modules installed in the RIO drops
-
Number of RIO drops scanned
-
Scan rate of the RIO drops
The processing capability without packet loss, including unicast, multicast, and broadcast frames management is limited for M580 CPU and BM•CRA31210.
Design the open Ethernet network architecture by taking into account that the overall traffic does not exceed the following limits:
M580 CPU:
15000 packets per second (pps)
BM•CRA31210:
8000 packets per second (pps)