Step
|
Action
|
Comment
|
---|---|---|
1
|
Connect the PC that is running the Control Expert OS Loader directly to one of the module ports.
|
Available ports:
|
2
|
Launch OS Loader.
|
Start → Programs → EcoStruxure Control Expert → OS Loader.
|
3
|
Click Next to continue.
|
Go directly to the first installation step.
|
4
|
Select the FTP communication driver and press Next to continue.
|
The next screen displays a list of devices discovered by OS Loader. It also displays the FTP address for each discovered device.
|
5
|
In the Target Address area, type the FTP Address of the 140 NOP 850 00 module that is the target of the upgrade.
|
—
|
6
|
Click Next to continue. Perform these tasks at the next installation screen: a Select Download OS to device. b Click the Browse button to navigate to and select the desired firmware upgrade file. |
—
|
7
|
Click Next. Perform these tasks at the next installation screen: a Compare the selected firmware File against the firmware already loaded in the Device. b Confirm that the Hardware ID for both the file and the device are the same |
—
|
8
|
Click Next. On the summary page, click Download.
|
The OS Loader displays the progress of the FTP session. The download is complete when it displays the word SUCCESS.
|
9
|
Click Close.
|
The firmware download is finished.
|
Step
|
Action
|
---|---|
1
|
Use the preceding instructions to upgrade the firmware for the 140 NOP 850 00 in the standby rack.
NOTE: During the firmware upgrade, the communications with the 140 NOP 850 00 module in the primary rack are not interrupted. |
2
|
When the firmware on the 140 NOP 850 00 in the standby rack is upgraded, perform a manual switch-over that gives the newly upgraded standby rack the role of primary rack.
|