Characteristics of the outputs of module TBX AMS 620
(Original Document)
General characteristics of the inputs
This table presents the characteristics of the inputs of module TBX AMS 620:
Module TBX AMS 620
Number of channels
6
Electrical range
+ or -10 V
0/5 V
0/20 mA
4/20 mA
Full scale (FS)
10 V
5 V
20 mA
20 mA
Resolution
11 bits + sign
12 bits
12 bits
12 bits
LSB
5,13 mV
1,30 mV
4,97 μA
4,97 μA
Converter
by successive approximation
Maximum error
at 25 °C
0,2 % FS
0,15 % FS
0,25 % FS
0,25 % FS
at 60 °C
0,26 % FS
0,22 % FS
0,43 % FS
0,43 % FS
Temperature drift
20 ppm (FS) °C
15 ppm (FS) °C
40 ppm (FS) °C
40 ppm (FS) / °C
Impedance
10 MΩ
10 MΩ
250 MΩ
250 MΩ
Time to read
one channel
5,3 ms
6 channels
42.4 ms
Permissible overload
voltage
+ or -30 V DC (voltage range)
current
30 mA ; + or -7.9 V (current range)
Digital filtering
1° order with configurable time constant
Linearization
automatic
Monotonocity
Yes
General characteristics of the outputs
This table presents the characteristics of the outputs of module TBX AMS 620:
Module TBX AMS 620
Number of channels
2
Range
+ or -10V
0/20 mA
0/40 mA
Full scale (FS)
10 V
20 mA
Resolution
11 bits + sign
11 bits
LSB
4,88 mV
9,76 μA
Load impedance
≥ 1 kΩ
≤ 600 Ω
Maximum error
at 25 °C
0,45 % FS
0,52 % FS
at 60 °C
0,75 % FS
0,98 % FS
Maximum drift
65 ppm (FS) / °C
103 ppm (FS) / °C
Update period
5 ms
Continuous overvoltage
+ or - 30 V
Monotonicity
Yes
Maximum leakage current
-
50 μA (0/20 mA)