Introduction to the TBX ASS 200 module
(Original Document)
General
The TBX ASS 200 base unit is an analog output module which has 2 isolated channels. It must be used with a TBX LEP 030 communicator.
This module can provide each output with the following ranges:
Technical specifications
The following table provides the technical specifications of the module.
TBX AMS 200
Supply voltage +SV
19,2 V DC to 60 V DC
Nominal voltage +SV
24 V DC
48 V DC
Current drawn at +SV by the ASS used as a basic module (1)
180 mA typically
257 mA max.
92 mA typically
132 mA max.
Additional current drawn from a basic module when the ASS module is used as an extension
15 mA typically
23 mA max.
8 mA typically
12 mA max.
Current drawn at +SV by the ASS used as an extension
162 mA typically
202 mA max.
84 mA typically
104 mA max.
Isolation
between channels
1500 V rms - 50/60 Hz for 1 min
between channels and ground (GND)
1500 V rms - 50/60 Hz for 1 min
between channel and supply
1500 V rms - 50/60 Hz for 1 min
Key:
(1)
In terms of consumption, do not forget to consider the current drawn at +SV by the TBX LEP 030 communication module from the basic module.