Characteristics of the inputs of module TBX DES 16C22
(Original Document)
General characteristics
This table presents the characteristics of the inputs of module TBX DES 16C22:
Module TBX DES 16C22
Nominal voltage IS
24 V DC
Current at 24 V
7 mA
Sensor power supply IS
19,2 V DC to 30 V DC
Voltage for ON state
≥ 11 V
Current at 11 V
≥ 6 mA
Voltage for OFF state
< 5 V
Current for OFF state
≤ 2 mA
Input impedance
3,4 kΩ
Switch-on time
fast filtering
5  to 8.5 ms
slow filtering
30  to 45 ms
Switch-off time
fast filtering
5  to 8.5 ms
slow filtering
30  to 45 ms
Permitted line resistance (2 wire proximity sensor)
100 Ω
Permitted line resistance (volt-free contact)
500 Ω
Permitted leakage resistance (2 wire proximity sensor)
(1)
Permitted leakage resistance (volt-free contact)
(1)
IEC standard 1131
Type 2
Compatibility with Telemecanique 2 wire proximity sensors
Yes
Compatibility with CENELEC 3 wire proximity sensors
Yes (2)
Compatible with TBX transistor outputs
Yes
Type of input
Current sink
Type of logic
Positive
Power dissipated per channel at ON state
0,17 W
Protection of +C terminals against overload or short‐circuit
Yes
Protection against a reverse polarity on IS
Yes: reverse diode in parallel (ext. fuse 2 A (quick blow))
Key:
IS
Power supply to sensors.
(1)
(2)
With a standard 3 wire proximity sensor, with a resistor in parallel, the open circuit fault corresponds to a break in the input/proximity sensor link, or in the +power supply (+Cs) of the 3 wire proximity sensor.
Note: the break in the - power supply to the proximity sensor (‐Cs) is not detected.