Module TBX EEP 1622
|
|
---|---|
Nominal voltage
|
24 V DC
|
Nominal current
|
7 mA
|
Sensor power supply
|
19,2 V DC to 30 V DC
|
Voltage for ON state
|
≥ 7 V
|
Current at 11 V
|
≥ 2 mA
|
Voltage for ON state
|
< 5 V
|
Current for OFF state
|
≤ 1.4 mA
|
Input impedance at 24 V
|
3,4 kΩ
|
Switch-on time
|
5 to 11 ms
|
Switch-off time
|
5 to 13 ms
|
Permitted line resistance (2 wire proximity sensor)
|
100 Ω
|
Permitted line resistance (volt-free contact)
|
500 Ω
|
IEC standard 1131
|
Type 1
|
Compatibility with Telemecanique 2 wire proximity sensors
|
Yes
|
Compatibility with CENELEC 3 wire proximity sensors
|
Yes
|
Compatible with TBX transistor outputs
|
Yes
|
Type of input
|
Resistive
|
Type of logic
|
Positive
|
Power dissipated per channel at ON state
|
0,17 W
|
Illustration
|
Terminal
|
Description
|
---|---|---|
Type M12 female connector (one per two channels).
![]() |
1
|
+24 V (supplied by module)
|
2
|
sensor signal, green LED (odd channel 1, 3, ..., 15)
|
|
3
|
0 V (supplied by module)
|
|
4
|
sensor signal, yellow LED (even channel 0, 2, ..., 14)
|
|
5
|
ground connection
|