Characteristics of the inputs of module TBX EEP 1622
(Original Document)
General characteristics
This table presents the characteristics of the outputs of module TBX EEP 1622:
Module TBX EEP 1622
Nominal voltage
24 V DC
Nominal current
7 mA
Sensor power supply
19,2 V DC to 30 V DC
Voltage for ON state
≥ 7 V
Current at 11 V
≥ 2 mA
Voltage for ON state
< 5 V
Current for OFF state
≤ 1.4 mA
Input impedance at 24 V
3,4 kΩ
Switch-on time
5  to 11 ms
Switch-off time
5  to 13 ms
Permitted line resistance (2 wire proximity sensor)
100 Ω
Permitted line resistance (volt-free contact)
500 Ω
IEC standard 1131
Type 1
Compatibility with Telemecanique 2 wire proximity sensors
Yes
Compatibility with CENELEC 3 wire proximity sensors
Yes
Compatible with TBX transistor outputs
Yes
Type of input
Resistive
Type of logic
Positive
Power dissipated per channel at ON state
0,17 W
Connections
The following table illustrates channel connection for module TBX EEP 1622
Illustration
Terminal
Description
Type M12 female connector (one per two channels).
1
+24 V (supplied by module)
2
sensor signal, green LED (odd channel 1, 3, ..., 15)
3
0 V (supplied by module)
4
sensor signal, yellow LED (even channel 0, 2, ..., 14)
5
ground connection