Characteristics of the inputs of module TBX EEP 08C22
(Original Document)
General characteristics
This table presents the characteristics of the outputs of module TBX EEP 08C22:
Module TBX EEP 08C22
Nominal voltage
24 V DC
Nominal current
6 mA
Sensor power supply
19,2 V DC to 30 V DC
Voltage for ON state
≥ 11 V
Current at 11 V
≥ 5 mA
Voltage for OFF state
< 6 V
Current for OFF state
≤ 2 mA
Input impedance at 24 V
3,4 kΩ
Switch-on time
5  to 8.5 ms
Switch-off time
5  to 8.5 ms
Permitted line resistance (2 wire proximity sensor)
100 Ω
Permitted line resistance (volt-free contact)
500 Ω
IEC standard 1131
Type 2
Compatibility with Telemecanique 2 wire proximity sensors
Yes
Compatibility with CENELEC 3 wire proximity sensors
Yes (leakage current ≥ 1 mA)
Compatible with TBX transistor outputs
Yes
Type of input
Current sink
Type of logic
Positive
Power dissipated per channel at state 1
0,17 W
Protection of  4 signal terminals against overload or short-citcuit
Yes
Protection per diode against a reverse polarity on +24 V
Yes
Connections
The following table illustrates channel connection for module TBX EEP 08C22
Illustration
Terminal
Description
Type M12 female connector (one per channel).
1
+24 V (supplied by module)
2
not connected
3
0 V (supplied by module)
4
sensor signal
5