Module TBX EEP 08C22
|
|
Nominal voltage
|
24 V DC
|
Nominal current
|
6 mA
|
Sensor power supply
|
19,2 V DC to 30 V DC
|
Voltage for ON state
|
≥ 11 V
|
Current at 11 V
|
≥ 5 mA
|
Voltage for OFF state
|
< 6 V
|
Current for OFF state
|
≤ 2 mA
|
Input impedance at 24 V
|
3,4 kΩ
|
Switch-on time
|
5 to 8.5 ms
|
Switch-off time
|
5 to 8.5 ms
|
Permitted line resistance (2 wire proximity sensor)
|
100 Ω
|
Permitted line resistance (volt-free contact)
|
500 Ω
|
IEC standard 1131
|
Type 2
|
Compatibility with Telemecanique 2 wire proximity sensors
|
Yes
|
Compatibility with CENELEC 3 wire proximity sensors
|
Yes (leakage current ≥ 1 mA)
|
Compatible with TBX transistor outputs
|
Yes
|
Type of input
|
Current sink
|
Type of logic
|
Positive
|
Power dissipated per channel at state 1
|
0,17 W
|
Protection of 4 signal terminals against overload or short-citcuit
|
Yes
|
Protection per diode against a reverse polarity on +24 V
|
Yes
|
Illustration
|
Terminal
|
Description
|
---|---|---|
Type M12 female connector (one per channel).
![]() |
1
|
+24 V (supplied by module)
|
2
|
not connected
|
|
3
|
0 V (supplied by module)
|
|
4
|
sensor signal
|
|
5
|
ground connection
|