Meaning of terminals of TBX distributed input/output modules
(Original Document)
Description
The following table provides the definition of discrete TBX module terminals (IP20).
Terminal
Comment
+C
TBX DMS 16P22 modules only.
This terminal, connected internally to +S (+24 V DC) serves as the common for 2 sensors. It is not protected against short‐circuits.
+C
TBX DMS 16P22 modules only.
This terminal, connected internally to +S (0 V DC) serves as the common for 2 preactuators.
+CA
This terminal, connected internally to +Os (a +24 V), is not protected against short‐circuits.
-CA
This terminal, connected internally to -Os (0 V DC) serves as the common for 2 preactuators.
Cn,
n+1
On relay output modules, this terminal serves as the common for 2 relays.
+Cs
This terminal, connected internally to +Is (a +24 V DC or a +48 V DC), serves as the common for 2 sensors. It is not protected against short‐circuits.
-Cs
This terminal, connected internally to -Is (0 V), serves as the common for two 3-wire proximity sensors.
+Csn,
n+1
Only for modules with wiring check function. This terminal, which supplies a +24  V DC protected against short-circuits, serves as the common for 2 sensors. It comes from +Is (+24  V DC).
In
Input.
I/On
TBX DMS 16P22 modules only.
This terminal can be configured as an Input or an Output.
+IS
+ input supply terminal: +24 V DC or +48 V DC
-IS
- input supply terminal: 0 V.
NC
Voltage free terminal: Not Connected.
N1
The two N1 terminals are connected together internally. They only exist on modules with 12 or 16 relay outputs.
On S
Output
+OS
+ output supply terminal: +24 V DC
-OS
- output supply terminal: 0 V.
+Osn,
n+1
TBX DMS 16C222 modules only.
This terminal supplies two 2A transistor outputs with +24 V DC.
+S
TBX DMS 16P22 modules only.
+ input and I/O supply terminal: +24 V DC.
-S
TBX DMS 16P22 modules only.
- input and I/O supply terminal: 0 V.
+SV
+ module supply terminal: +24 V DC or +48 V DC. This powers the communication module and the I/O interface of the base or extension module.
-SV
- module supply terminal: 0 V. This powers the communication module and the I/O interface of the base or extension module.