Step
|
Action
|
Comment
|
---|---|---|
1
|
Expand (+) EIO Bus in the Control Expert Project Browser.
|
Path: Project Browser → EIO Bus → Quantum S908 remote drop.
|
2
|
In the EIO Bus, double-click the Quantum S908 remote drop.
|
The Quantum S908 remote drop window appears. It contains the parameter tabs for the drop.140CRA31908
|
3
|
Select the Parameter tab.
|
–
|
Parameter
|
Comment
|
---|---|
Device Name
|
The device name of the device includes a fixed device prefix and a number provided by the rotary switch. Valid device names conform to this structure (where QSA represents the 140CRA31908 module): 140QSA_xxx
Remember that xxx equals the three-digit value selected on the rotary switches, so the device name includes the device prefix (140QSA) plus that value.
When the device is placed on the X80 remote drop, the number is set to the device number. The device number does not change when the device moves to a new location.
Valid device numbers are unique within the application. A message like this appears when analysis reveals redundant device numbers:
{EIO Bus (2)140CRA31908): Device name is not unique
NOTE: The device number does not change if you move the remote drop, but you can modify the number. However, if you modify the number, the link breaks between the device name and the remote drop number. Schneider Electric recommends that you allow the remote drop number to equal the device name, even if it can be modified. |
IP Address
|
The IP address of the 140CRA31908 module can be changed only from the Ethernet Network Manager. (In the Project Browser of your Control Expert application, double-click your Ethernet network to open the manager, or right-click Ethernet Network → Open.
|
Sub Network
|
|
Update IP/DHCP configuration
|
Click this link to view the Ethernet Network window.
|
Parameter
|
Comment
|
---|---|
Hold up time
|
Valid values for the Hold up time are 50...65530 (ms). This value represents the time that device outputs are maintained in their current states after a communication disruption and before taking their fallback values.
|
![]() |
UNINTENDED EQUIPMENT OPERATION
Do not configure a holdup time value that is less than the recommended minimum value for standalone or redundant systems:
Failure to follow these instructions can result in death, serious injury, or equipment damage.
|
Parameter
|
Comment
|
---|---|
Custom RPI
|
Select this check box to configure the CRA->CRP RPI value.
|
CRA->CPU RPI (inputs)
|
The RPI is the input refresh rate at which the 140CRA31908 module sends inputs to the CPU EIO scanner service. The RPI is set in the subscribe field for the 140CRA31908 module on the X80 remote drop.
NOTE:
|
CPU->CRA RPI (outputs)
(See note below.)
|
Outputs are passed from the CPU with EIO scanner service to the 140CRA31908 module. Set the output refresh rate with the Application Trigger value (CPU->CRA RPI) at the end of the CPU MAST task:
You cannot edit this value. All outputs are published synchronously or at the execution of the MAST task:
|