Configuration

Follow these steps to modify the Service Port configuration of an online 140CRA31200 or BMXCRA312•0 adapter module:

Step

Action

1

Launch the EtherNet/IP Explicit Message window.

2

Assign these Device Services parameters:

  • Address:

    • IP Address: Enter the IP address of the adapter with the SERVICE port you want to configure.

    • Class: 0x400

    • Instance: 1

  • Service:

    • Name: Set_Attribute_Single

3

Set the Port Control value:

NOTE:
  • To set the UINT value of 2, set the data field to 02 00 (low byte/high byte).

  • If you enter 2 (port mirroring) in Attribute, refer to the next table.

  • In port mirroring mode, the SERVICE port acts like a read-only port. That is, you cannot access devices (ping, connection to Control Expert, etc.) through the SERVICE port.

4

Leave the default values for these parameters:

  • Enter Path(hex): Leave this check box unselected.

  • Repeat(500ms): Leave this check this check box unselected.

  • Messaging: Select Unconnected.

5

Press Send to Device.

Port Mirroring: Use these steps only if you chose 2 (port mirroring) for the Port Control value (above):

Step

Action

1

Set the Port Control value:

2

Accept the default values for other parameters (as before).

3

Press Send to Device.