An isolated distributed I/O network is not part of the remote I/O network. It is an Ethernet-based network containing on a copper wire running from a single port connection. If you use dual-port distributed I/O devices that support , you can connect the devices in a daisy-chain loop to the 2 device network ports (ETH 3 and ETH 4) on the 140NOC78000 distributed I/O head module. There is no interlink to the .
Attaching an Isolated Distributed I/O Network
To attach an isolated distributed I/O network to a Quantum EIO system:
Step
|
Action
|
1
|
Install up to six 140NOC78000 distributed I/O head modules on the local rack, one module for each isolated network desired.
|
2
|
Connect the device network port (ETH 4) of each 140NOC78000 module to each distributed I/O network.
|
3
|
If you use dual-port devices that support RSTP, then you can connect the devices in a daisy chain loop to both device network ports (ETH 3 and ETH 4) on the 140NOC78000 distributed I/O head module.
|
4
|
The 140NOC78000 modules are not connected to any other head module on the local rack.
|
The following graphic shows multiple isolated distributed I/O networks. The 140NOC78000 distributed I/O head modules are not linked to the 140CRP31200 remote I/O head module on the .
1
140CRP31200 remote I/O head module
2
140NOC78000 distributed I/O head modules
3
distributed I/O clouds, which do not communicate with the Quantum EIO networks
NOTE:
-
A 140NOC78000 module on the local rack attaches the controller to the isolated distributed I/O network.
-
A cloud can have a downloaded predefined configuration and a single connection to the 140NOC78000 module on the local rack and a ring of dual-port distributed I/O devices that support .