Powering Up Modules Without a Downloaded Application
Original instructions
140CRP31200 IP Address
In the absence of an application, the 140CRP31200 remote I/O head module uses the IP address that is based on the MAC address printed on the front of the module. You can configure the IP address in Control Expert as detailed in the Quantum EIO Remote I/O Modules Installation and Configuration Guide when you have downloaded an application.
•••CRA312•0 IP Address
In the absence of an application, the •••CRA312•0 remote I/O adapter module unsuccessfully requests an IP address from the 140CRP31200 head module. The adapter module then requests an IP address from the MAC address printed on the front of the module. The module continues in this cycle because it does not have a valid configuration. This Not Configured state is indicated by the LED display on the front of the module. There are no exchanges with the PLC. Physical outputs of I/O modules in the remote I/O drops are in the fallback state (output forced at 0).