Security
Original instructions
Security and HTTP, FTP, and TFTP Services
The module uses HTTP services to provide access to its embedded Web pages. The module uses FTP and TFTP services to support various features including firmware upgrades, FDR services, and Ethernet remote IO.
The module’s HTTP, FTP, and TFTP services can be disabled or enabled using the DTM Browser Security screen.
HTTP, FTP, and TFTP services are disabled by default in DTM instances created using PlantStruxure EIO Version 1.5 and Unity Pro 8.0 or later. They are enabled by default in instances created using earlier versions of Unity Pro.
NOTE: Unity Pro is the former name of Control Expert for version 13.1 or earlier.
You can use Control Expert to enable or disable HTTP, FTP, and TFTP services as described in the following procedure.
If the HTTP, FTP, or TFTP services have been enabled with Control Expert, they can also be enabled or disabled at run time using an MBP_MSTR block with operation code FFF0 (hex).
Using Control Expert to Enable and Disable Firmware Upgrade & FDR and Web Access Services
Perform the following steps to enable or disable FTP/TFTP or HTTP services on the module.
Step
Action
1
In the Control Expert main menu, select Tools → DTM Browser to open the DTM Browser.
2
Confirm that the DTM you want to use is not connected to the actual communication module or device. If necessary, disconnect the DTM from the module or device.
3
In the DTM Browser, select the module. Right-click and select Open to open the Device Editor.
4
Click the Security node in the navigation tree in the left panel to open the Security screen.
5
On the Security screen, choose the appropriate setting: (Enabled or Disabled) for the service or services.
6
Click:
  • Apply to save the changes and keep the window
    - or -
  • OK to save the changes and close the window
The edits will not take effect until they are successfully downloaded from your PC to the CPU and from the CPU to the communication modules and network devices.