Diagnostics Available through the CPU
Original instructions
Introduction
System diagnostics are performed locally on the CPU with system bits (%S) and system words (%SW).
Local Rack Diagnostics
Local rack diagnostics are accessible for 140 NOC 78• 00, 140 NOC 771 ••, and 140 NOE 771 •• modules within the standard system words (%SW180 to %SW183).
System Bits and Words
This table describes new or modified system bits and words that represent detected errors:
System Bits/Words
Symbol
Description
%S117
EIOERR
detected remote I/O error on the Ethernet I/O network
%SW101
EIO_ CCOTF_COUNT
EIO CCOTF counting status register
%SW108
FORCED_DISCRETE_COUNT
forced bit counting status register
%SW152 ... %SW153
EIO_DROP_ERROR
detected Ethernet remote I/O drop status
The bit is set to 0 if at least one I/O module in the drop as a detected error.
The bit is set to 1 if all modules are operating properly.
  • %SW152.0: drop #1
  • %SW152.1: drop #2
  • ........
  • %SW153.14: drop #31
%SW172 ... %SW175
EIO_CONNECT_STATUS
Ethernet I/O communication health status for drops in standalone and primary systems
%SW176 ... %SW179
SDBY_EIO_CONNECT_STATUS
Ethernet I/O communication health status for drops in standby systems
%SW641 ... %SW702
EIO_MOD_HEALTH
Ethernet remote I/O module health bit status
NOTE: Refer to the EcoStruxure™ Control Expert, System Bits and Words, Reference Manual for a detailed explanation of system bits and words.