EtherNet/IP Connection Information
Original instructions
Overview
Use this read-only page to view connection properties for the remote device. An EtherNet/IP connection provides a communication link between two or more devices. Properties for a single connection are configured in the DTMs for each of the connected devices—typically a communication module and a remote device. The read-only properties viewable in this page can be configured in the General page of the connection node configuration page for the DTM of the remote device.
To open this page, in the left pane of the Device Editor expand the navigation tree and, under the Device List node, select <remote device><connection>, where:
Remote Device Connection Properties
A connection to a remote Schneider Electric device can present the following properties:
Setting
Description
RPI
The refresh period for this connection, in milliseconds.
Input size
The number of bytes reserved for input data, from 0 to 505.
Input mode
The transmission type:
  • Multicast
  • Point to Point
Input type
Ethernet packet type—fixed or variable length—to be transmitted.
NOTE: The Ethernet communication module supports only Fixed length packets.
Input priority
The transmission priority. The value depends upon the device DTM. Values can include:
  • Low
  • High
  • Scheduled
Input trigger
The transmission trigger. Values can include:
  • Cyclic
  • Change of state or application
Output size
The number of bytes reserved for output data, from 0 to 509.
Output mode
The transmission type:
  • Multicast
  • Point to Point
Output type
Ethernet packet type—fixed or variable length—to be transmitted.
NOTE: The Ethernet communication module supports only Fixed length packets.
Output priority
The transmission priority. The value depends upon the device DTM. Values can include:
  • Low
  • High
  • Scheduled