Controlling and Timing
Original instructions
Controlling the Module
Hardware inputs from the field can be used to:
Hardware inputs from the field and software commands are used together to:
Hardware inputs from the field or software commands can be used to:
Software commands can be used to:
Timing Diagrams
The following figure shows the EHC20200 timing diagrams.
Timing Parameter Table
The following table shows the EHC20200 timing parameters.
Timing Parameters
Limits
Filter 200 Hz
Filter 200 Hz
No Filter
500 khz
Tdly1
Count to Output Assertion Delay (MAX)
4.8 ms
40 μs
Tdly2
Preset/Reset to Output Delay (MAX)
4.8 ms
40 μs
Tpw1
Count/Reset Pulse Width (MIN)
2.5 ms
1 μs
Tpw2
Preset Pulse Width (MIN)
2.5 ms
500 μs
Tst
Enable/Reset/Preset to Count Setup Time (MIN)
2.5 ms
2 μs
Thold
Enable/Reset to Count Hold Time (MIN)
2.5 ms
2 μs
NOTE: The timing parameter limits are measures at the module field terminal connector at the logic low threshold level.