Module Type
|
High Speed Counter Module
|
Number of Channels
|
2
|
External Power
|
19,2 ... 30 VDC, 24 VDC nominal, 50 mA reqired plus the load current for each output.
|
Power Dissipation
|
4+(0.4 x total modul load current)
|
Bus Current required
|
650 mA
|
I/O Map
|
6 words IN, 6 words OUT
|
Isolation (channel to bus)
|
1780 VAC rms for 1 minute
|
Fault detection
|
Blown fuse detect; loss of 1A, 1B, 2A, 2B output field power
|
Fusing
|
internal: 2.5 (P/N 043503948 or equivalent)
external: user discretion
|
Backplane Support
|
Local, remote or distributed
|
Operating mode
|
incremental or quadratur
|
Input voltage
|
30 V max. continuous
|
Data formats
|
16 bit counter: 65.535 Decimal
32 bit counter: 2.147.483.647 Decimal
|
Operating mode
|
incremental or quadratur
|
Input voltage
|
30 V max. continuous
|
Input resistence
|
10 kohms
|
single ended mode
|
VREF supply
|
On state
|
Off state
|
5 VREF DC
|
0 ... 2 V
|
3.5 ... 5.0 V
|
|
12 VREF DC
|
0 ... 5 V
|
7 ... 12 V
|
|
24 VREF DC
|
0 ... 11 V
|
13 ... 24 V
|
|
differential mode
|
1.8 VDC minimum
|
FET Switch ON
|
supply - 0.4 V
|
FET Switch OFF
|
0 VDC (ground reference)
|
Max. load current (each output)
|
0,5 A
|
Output off state Leackage
|
0,4 A max @ 30 VDC
|
Output on state voltage drop
|
0.4 VDC @ 0,5 A
|
Output Levels
|
1A, 2A, 1B, 2B
|
Output Protection
|
36 V transorb for transient voltage suppression
|