Specifications
Original instructions
General Specifications
General Specifications
Module Type
High Speed Counter Module
Number of Channels
2
External Power
19,2 ... 30 VDC, 24 VDC nominal, 50 mA reqired plus the load current for each output.
Power Dissipation
4+(0.4 x total modul load current)
Bus Current required
650 mA
I/O Map
6 words IN, 6 words OUT
Isolation (channel to bus)
1780 VAC rms for 1 minute
Fault detection
Blown fuse detect; loss of 1A, 1B, 2A, 2B output field power
Fusing
internal: 2.5 (P/N 043503948 or equivalent)
external: user discretion
Backplane Support
Local, remote or distributed
Counter Inputs
Counter inputs
Operating mode
incremental or quadratur
Input voltage
30 V max. continuous
Data formats
16 bit counter: 65.535 Decimal
32 bit counter: 2.147.483.647 Decimal
Discrete Inputs
Discrete inputs
Operating mode
incremental or quadratur
Input voltage
30 V max. continuous
Input resistence
10 kohms
Input threshold
Input threshold
single ended mode
VREF supply
On state
Off state
5 VREF DC
0 ... 2 V
3.5 ... 5.0 V
12 VREF DC
0 ... 5 V
7 ... 12 V
24 VREF DC
0 ... 11 V
13 ... 24 V
differential mode
1.8 VDC minimum
Discrete Outputs
Discrete outputs
FET Switch ON
supply - 0.4 V
FET Switch OFF
0 VDC (ground reference)
Max. load current (each output)
0,5 A
Output off state Leackage
0,4 A max @ 30 VDC
Output on state voltage drop
0.4 VDC @ 0,5 A
Output Levels
1A, 2A, 1B, 2B
Output Protection
36 V transorb for transient voltage suppression