UNINTENDED EQUIPMENT OPERATION
Do not exceed any of the rated values specified in the following tables.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
|
Bus Current Required
|
700 mA
|
Power Dissipation (Typical)
|
5 W
|
Inrush Current
|
1 A typical @ 5 Vdc
|
Data Transfer Rate
|
1.544 Mb for remote I/O with Manchester encoded data
|
Bit Error Rate
|
10-9 over specified Optical Receiver Dynamic Range
|
Optical Interface
|
ST-Type connector
|
Wavelength
|
820 nm
|
Power Loss Budget
(includes 3 dB of system margin)
|
50/125 µm fiber –7.0 dB
62.5/125 µm fiber –11 dB
100/140 µm fiber –16.5 dB
|
Maximum Distance for Point–to–Point Connection
|
2 km over 50/125 µm fiber @ 3.5 dB/km
3 km over 62.5/125 µm fiber @ 3.5 dB/km
3 km over 100/140 µm fiber @ 5 dB/km
|
Limits in Bus or Self-Healing Ring Configurations
|
12 fiber optic repeater modules with a maximum length of fiber optic cables of 16 km (back-loop included in Self-healing ring configuration).
NOTE: The maximum length is between the CRP module (the farther one in a Hot Standby (HSBY) system) and the last CRA module. |
Coaxial Interface
|
F type female connector with a right-angle F adapter connector
NOTE: Required torque to fasten the right-angle F adapter is 0.46...0.60 N•m (4.1...5.3 lbf-in). |
Coaxial Termination
|
Internal 75 ohms
|
Coaxial Shield
|
Tied to ground
|
Coaxial Dynamic Range
|
35 dB
|
Coaxial Sensitivity
|
70 mV pk-pk max
|
Relay Diagnostic
|
Rated at 220 Vac 6 A / 30 Vdc 5 A
|
NOTICE
|
DESTRUCTION OF ADAPTER
Failure to follow these instructions can result in equipment damage.
|
Optical Power (Measured with 1 m test fiber)
|
–13.0...–20.0 dBm average power in 50/125 µm fiber cable
–10.0...–16 dBm average power in 62.5/125 µm fiber cable
–4.0...–10.5 dBm average power in 100/140 µm fiber cable
|
Rise/Fall Time
|
20 nsec or better
|
Silence (OFF Leakage)
|
–43 dBm
|
Receiver Sensitivity
|
–30 dBm average power
|
Dynamic Range
|
20 dB
|
Detected Silence
|
–36 dBm
|
MTBF
|
1,300,000 hours (minimum) @ 30 °C, assuming fixed ground and component stress within maximum specifications.
|