Explicit Adjustment Parameters %MWAdjust
Original instructions
Explicit Adjustment Parameters %MWAdjust
Explicit Adjustment Parameters %MWAdjust
Object
Type
Symbol
Detail
%MDr.m.c.14
DINT
SW_High_Limit
Software Pulse Number High Limit
Value from -2,147,483,647 to 2,147,483,647
Default: 2,147,483,647
%MDr.m.c.16
DINT
SW_Low_Limit
Software Pulse Number Low LimitValue from -2,147,483,648 to 2,147,483,646
Default: -2,147,483,648
%MWr.m.c.18
UINT
Start_Freq
0: No use of start frequency parameter (Default)
Otherwise: value in Hz from 1 to 65,535
%MWr.m.c.19
UINT
Stop_Freq
No use of stop frequency parameter (Default)
Otherwise: value in Hz from 1 to 65,535
%MWr.m.c.20
UINT
Acc_Rate
For all profiles except Frequency Generator
Value from 10 to 32,500
Default: 100
%MWr.m.c.21
UINT
Dec_Rate
For all profiles except Frequency Generator
Value from 10 to 32,500
Default: 100
%MWr.m.c.22
UINT
Emergency_Dec_Rate
Deceleration rate used in case of emergency stop (limits crossed, errors)
Value from 10 to 32,500
Default: 100
%MWr.m.c.23
UINT
Homing_Velocity
For Homing Command:
Value in Hz from 1 to 65,535
Default: 1
%MWr.m.c.24
UINT
Homing Time Out Value
For Homing Command:
Only used when Homing I/O Settings parameter is set to 2.
Value in ms from 0 to 65,535
Default: 65,535
%MWr.m.c.25
INT
Hysteresis (slack)
When Output mode is A/B Phases (reversed or not):
Defines the numerical hysteresis to apply on PTO outputs in case of change of direction
Value in pulses from 0 to 255
Default: 0
%MWr.m.c.26
INT
Reserved
Reserved