Storage, document and simulation
(Original Document)
Storage
When you have debugged your program in connected mode, you must carry out the following save operations:
Documentation
The documentation for the axes control application is included in the complete documentation for the Control Expert application. This documentation allows you to group in a file:
Simulation
To operate the channels of the TSX CFY module, all you need is the Telefast discrete simulator strip, reference ABE-6TES160, supplied by the 24 volts available on the rack supply, and to connect it directly to the TSX CFY’s auxiliary I/O HE10 connector via a ribbon cable.
For channel 0, add a level 1 to inputs 2, 4 and 5 (emergency stops and end of runs).
For channel 1 (only TSX CFY 21), inputs 8, 10 and 11. Leave the level 0 everywhere else.
When configuring the axis control channel, check the box drive inversionsmonitor input. This supports operation in the absence of any connection to the SUB D translator.
Confirm
How to carry out simulation with a TSC CFY
To operate the channels of the TSX CFY module, all you need is the Telefast discrete simulator strip, reference ABE-6TES160, supplied by the 24 volts available on the rack supply, and to connect it directly to the TSX CFY’s auxiliary I/O HE10 connector via a ribbon cable.
Step
Action
1
For channel 0, add a level 1 to inputs 2, 4 and 5 (emergency stops and end of runs).
2
For channel 1 (only TSX CFY 21), add a level 1 to inputs 8, 10 and 11. Leave the level 0 everywhere else.
3
When configuring the axis control channel, check the box drive inversionsmonitor input. This supports operation in the absence of any connection to the SUB D translator.
4
Confirm the channel in the implementation screen in manual mode.
5
Use the buttons JOG+ or JOG- to simulate movements of the moving part.