Monitoring Sensor/Pre-sensor Voltage
(Original Document)
General
The supply for the actuators / pre-actuators is monitored by the module to signal to the processor any malfunction, which could lead to incorrect working order.
Table of characteristics:
Electrical characteristics
Symbol
Value
Units
Voltage for OK state
Uok
> 18
V
Voltage for faulty state
Udef
< 14
V
Immunity OK --> Error
Im.off
> 1
ms
Immunity error --> OK
Im.on
> 1
ms
Inclusion of error
Toff
< 10
ms
Inclusion of non-error
Ton
< 10
ms