Correspondence Between TELEFAST Terminals and HE10 Connector
(Original Document)
General
This table shows the correspondence between TELEFAST terminals and the module’s HE10 connector:
TELEFAST screw terminal block
(Terminal No.)
HE10 20-pin connector
(Pin No.)
Kind of signal
100
1
COM0
closed contact =
variable speed controller confirmation
101
2
VALR0
102
3
nc
103
4
COM1
104
5
VALR1
105
6
nv
106
7
COM2
107
8
VALR2
108
9
nc
109
10
COM3
110
11
VALR3
111
12
nc
112
13
OK_VAR0
VARiable OK =
voltage presence
of the encoder supply
113
14
OK_VAR1
114
15
OK_VAR2
115
16
OK_VAR3
+ 24 VDC
17
Auxiliary input sensor supply
- 0 VDC
18
+ 24 VDC
19
- 0 VDC
20
1
Terminals 200 to 215 at +24 VDC
2
3
Terminals 200 to 215 at –0 VDC
4
200...215
Connecting shared sensors to:
  • +24 VDC if terminals 1 and 2 are connected,
  • - 0 VDC if terminals 3 and 4 are connected
300...315
On the optional ABE-7BV20 bar, the terminals that can be used as a shared sensor must be connected by a wire to the shared voltage.
(1) nc = not connected.