Adjusting the Inversion Parameter
(Original Document)
Adjustment Procedure
Determine the inversion parameter as follows:
Action to be Taken
The following table shows the action to be taken, according to the change in position and value. This depends on the voltage (positive or negative) which has been defined for the analog output:
Analog output
Position
Measurement
Action to be taken
Positive
Increase
Increase
None (connection OK)
Positive
Increase
Decrease
Invert the measurement
Positive
Decrease
Decrease
Invert the setpoint
Positive
Decrease
Increase
Invert the setpoint and the measurement
Negative
Decrease
Decrease
None (connection OK)
Negative
Decrease
Increase
Invert the measurement
Negative
Increase
Increase
Invert the setpoint
Negative
Increase
Decrease
Invert the setpoint and the measurement
NOTE: If the offset is greater than 100 mV, you must first adjust it before proceeding.