Module type
|
6 inputs / 3 outputs, 120VAC
|
Operating Voltage
|
120 VAC
|
Range
|
85 ... 132 VAC @ 47 ... 63 Hz
|
Current
|
125 mA
|
Point to Point
|
None
|
I.O points to communication adapter
|
1250V RMS for one minute
|
Module field power to communication adapter
|
1250V RMS for one minute
|
Module power to I.O field power
|
1250V RMS for one minute
|
Field input to field input
|
1250V RMS for one minute
|
Modbus Port RS485 to communication adapter
|
Not isolated
|
Internal (replaceable)
|
2.5 A slow-blow (Wickmann 195125000 or equivalent)
|
Internal (non-replaceable)
|
200 mA slow-blow
|
External (field power)
|
2 A slow-blow (Wickmann 195120000 or equivalent)
|
External (module power)
|
200 mA slow-blow (Wickmann 195020000 or equivalent)
|
Immunity
|
IEC 1131-2
|
Emissions
|
EN 50081-2
|
Agency Approvals
|
UL, CSA, CE FM Class 1, Div. 2 pending
|
Width
|
125 mm (4.9 in)
|
Depth (with no adapter)
|
52 mm (2.05 in)
|
Length
|
141.1 mm (5.6 in) no or one busbar
159.5 mm (6.3 in) two busbars
171.5 mm (6.75 in) three busbars
|
Weight
|
284 g (10 oz)
|
Number of Points
|
6
|
Number of Groups
|
1, Non-isolated
|
Points per Group
|
6
|
For range 47 ... 53 Hz
|
|
ON Voltage
Off Voltage
ON current
OFF current
|
85VAC
20VAC
5.5mA rms
1.9mA rms
|
For range 57 ... 63 Hz
|
|
ON Voltage
Off Voltage
ON current
OFF current
|
79VAC
20VAC
5.5mA rms
1.9mA rms
|
Absolute Maximum Input
|
132VAC rms continuous
|
Input Response
|
1 line cycle maximum ON to OFF,
1 line cycle maximum OFF to ON
|
Internal Impedance
|
12k ohms (nominal) @ 60Hz, predominantly capaci tive
|
Input Protection
|
Resistor limited
|
Number of Points
|
3
|
Number of Groups
|
1 fuse group
|
Points per Group
|
3
|
Output Voltage
|
85 ... 120 ... 132 VACVAC @ 47 ... 63 Hz
|
Surge Voltage
|
150 VAC for 10 sec
200 VAC for 1 cycle
|
On State Voltage Drop
|
1.5 VAC max @ 0.5 A
|
Output (Load) Current
|
0.5 A / point,
1.5 A / module
|
Minimum Output Current
|
30 mA
|
Maximum Surge Current (rms)
|
7.5 A per point, one cycle
5 A per point, two cycles
|
Output Protection
|
RC snubber suppression, varistor
|
Leakage Current
|
1.9 mA @ 120 VAC
|
Applied dV / dT
|
400 V / microseconds
|
Response Time
|
0.5 of one line cycle max OFF to ON
0.5 of one line cycle max ON to OFF
|
Baud
|
9600, 19200
|
Parity
|
Even, odd or none
|
Mode/data bits
|
8 bit RTU, 7 bit ASCII
|
Stop bit
|
1 or 2
|
Modbus Address
|
0 ... 247
|
RS485
|
2 or 4 wire
|
Timeout
|
150ms (after transmission, waiting for reception)
|
Test
|
Spec Reference
|
Conditions/Levels
|
---|---|---|
Radiated
|
EN61000-4-3
|
80 ... 1000Mhz, 10V/M
|
Fast transients
|
EN61000-4-4
|
1kV, CM, cap clamp
|
Surge withstand (transients)
|
EN61000-4-5
|
1kV, CM, 42Ω source Z
|
Electrostatic discharge
|
EN61000-4-2
|
8kV, air discharge, 4kV, contact
|
Conducted RF
|
ENV61000-4-6
|
0.15 ... 80Mhz 10 VRMS
|
Pulsed modulated field
|
ENV 50140
|