Module type
|
10 discrete inputs in 1 group
8 relay outputs as normally open contacts in 2 groups, 4 pts/group
|
Supply voltage
|
24 VDC
|
Supply voltage range
|
20...30 VDC
|
Supply current consumption
|
max. 250 mA at 24 VDC
|
Power dissipation
|
6 W + (# of input points on x .144 W)
|
I/O map
|
1 input word
1 output word
|
Type of Load
|
Suppression Device
|
Minimum Component Rating
|
|
---|---|---|---|
AC circuits
|
50 Ω resistor in series with a 0.47 μfd nonpolarized capacitor across the load
|
for 120 VAC-powered loads
|
200 VAC
|
for 220 VAC-powered loads
|
400 VAC
|
||
DC circuits
|
a reverse-biased clamping diode across the load
|
2 A and greater than twice the maximum load voltage
|
Input to input
|
none
|
Output group to output group
|
1 780 VAC RMS
|
Input to output
|
1 780 VAC RMS
|
Output group to communication adapter
|
1 780 VAC RMS
|
Field to communication adapter
|
Defined by communication adapter type
|
Internal
|
none
|
External: operating voltage (L+)
|
1 A slow-blow (Bussmann GDC-1A or equivalent)
|
External: input voltage (1L+)
|
max. 4 A fast-blow (Wickmann 19193-4A or equivalent)
|
External: output voltage (1L1, 2L1)
|
According to the supply of the connected actuators–not to exceed 8 A slow-blow/ group.
|
Immunity
|
IEC 1131-2
Surge on auxiliary power supply AC 2 KV to PE, 1 KV to differential surge on auxiliary power supply DC 0.5 KV,
|
Emissions
|
EN 50081-2
|
Agency approvals
|
UL, CSA, CE, FM Class 1 Div. 2 pending
|
Width
|
125 mm (4.9 in)
|
Depth (with no adapter)
|
40 mm (1.54 in)
|
Length
|
141.5 mm (5.5 in) no or one busbar
159.5mm (6.3 in) two busbars
171.5 mm (6.75 in) three busbars
|
Weight
|
260 g (0.57lb)
|
Number of points
|
10
|
Number of groups
|
1
|
Signal type
|
True High
|
IEC 1131 type
|
1+ (See Appendix Input Voltage and Current Thresholds for definitions of IEC input types.)
|
ON voltage
|
+11 ... +30 VDC
|
OFF voltage
|
-3 ... +5 VDC
|
Input current
|
2.5 mA minimum ON (6 mA at 24 VDC)
1.2 mA maximum OFF
|
Input voltage range
|
-3 ... +30 VDC
|
Input resistance
|
4 kOhm
|
Response time
|
2.2 ms OFF to ON
3.3 ms ON to OFF
|
Output type
|
Relay normally open output
|
|
Number of points
|
8
|
|
Number of groups
|
2
|
|
Points per group
|
4
|
|
Current capacity
|
20 VDC
|
> 5 mA (but only for new contacts)
max 2 A (switching current <= 5 A) ohmic load
max 1 A (L/R <= 40 ms) inductive load
|
115 VDC
|
max. 0.5 A (switching current <= 1.5 A) ohmic load
max. 0.15 A (L/R <= 40 ms) inductive load
|
|
24 VAC
|
max. 2A (switching current <= 5 A) cos = 1
max. 1 A cos = 0.5
|
|
230 VAC
|
max. 2A (switching current <= 5 A) cos = 1
max. 1 A cos = 0.5
|
|
Relay type
|
Normally Open
|
|
Leakage current (output out)
|
< 1.2 mA @ 230 VAC
|
|
Fault sensing
|
These contacts have an internal suppressor circuit.
|
|
Fault reporting
|
None
|
|
Error indication
|
None
|
|
Response time (resistive load / 0.5 A)
|
10 ms @ 60 Hz OFF to ON 10 ms @ 60 Hz ON to OFF
|
|
Maximum switching cycles
|
> 3 x 106 (mechanical)
>=1 x 105 (inductive load with external protective circuitry)
|