Specifications
Original instructions
Overview
This section contains specifications for the 170 ADM 390 30 I/O base.
General Specifications
Module type
10 discrete inputs in 1 group
8 relay outputs as normally open contacts in 2 groups, 4 pts/group
Supply voltage
24 VDC
Supply voltage range
20...30 VDC
Supply current consumption
max. 250 mA at 24 VDC
Power dissipation
6 W + (# of input points on x .144 W)
I/O map
1 input word
1 output word
Protective Circuit Required
To reduce the effects of radiated noise, you must add snubbing components across inductive load devices. The following table provides generic selection guidelines.
Type of Load
Suppression Device
Minimum Component Rating
AC circuits
50 Ω resistor in series with a 0.47 μfd nonpolarized capacitor across the load
for 120 VAC-powered loads
200 VAC
for 220 VAC-powered loads
400 VAC
DC circuits
a reverse-biased clamping diode across the load
2 A and greater than twice the maximum load voltage
Consult relay and contactor manufacturers’ catalogs for commercial suppression devices matched to your particular products.
Isolation
Input to input
none
Output group to output group
1 780 VAC RMS
Input to output
1 780 VAC RMS
Output group to communication adapter
1 780 VAC RMS
Field to communication adapter
Defined by communication adapter type
Fuses
Internal
none
External: operating voltage (L+)
1 A slow-blow (Bussmann GDC-1A or equivalent)
External: input voltage (1L+)
max. 4 A fast-blow (Wickmann 19193-4A or equivalent)
External: output voltage (1L1, 2L1)
According to the supply of the connected actuators–not to exceed 8 A slow-blow/ group.
EMC
Immunity
IEC 1131-2
Surge on auxiliary power supply AC 2 KV to PE, 1 KV to differential surge on auxiliary power supply DC 0.5 KV,  
Emissions
EN 50081-2
Agency approvals
UL, CSA, CE, FM Class 1 Div. 2 pending
Physical Dimensions
Width
125 mm (4.9 in)
Depth (with no adapter)
40 mm (1.54 in)
Length
141.5 mm (5.5 in) no or one busbar
159.5mm (6.3 in) two busbars
171.5 mm (6.75 in) three busbars
Weight
260 g (0.57lb)
Discrete Inputs
Number of points
10
Number of groups
1
Signal type
True High
IEC 1131 type
1+ (See Appendix Input Voltage and Current Thresholds for definitions of IEC input types.)
ON voltage
+11 ... +30 VDC
OFF voltage
-3 ... +5 VDC
Input current
2.5 mA minimum ON (6 mA at 24 VDC)
1.2 mA maximum OFF
Input voltage range
-3 ... +30 VDC
Input resistance
4 kOhm
Response time
2.2 ms OFF to ON
3.3 ms ON to OFF
Relay Outputs
Output type
Relay normally open output
Number of points
8
Number of groups
2
Points per group
4
Current capacity
20 VDC
> 5 mA (but only for new contacts)
max 2 A (switching current <= 5 A) ohmic load
max 1 A (L/R <= 40 ms) inductive load
115 VDC
max. 0.5 A (switching current <= 1.5 A) ohmic load
max. 0.15 A (L/R <= 40 ms) inductive load
24 VAC
max. 2A (switching current <= 5 A) cos = 1
max. 1 A cos = 0.5
230 VAC
max. 2A (switching current <= 5 A) cos = 1
max. 1 A cos = 0.5
Relay type
Normally Open
Leakage current (output out)
< 1.2 mA @ 230 VAC
Fault sensing
These contacts have an internal suppressor circuit.
Fault reporting
None
Error indication
None
Response time (resistive load / 0.5 A)
10 ms @ 60 Hz OFF to ON 10 ms @ 60 Hz ON to OFF
Maximum switching cycles
> 3 x 106 (mechanical)
>=1 x 105 (inductive load with external protective circuitry)