Type
|
Part Number
|
---|---|
Screw-in
|
170 XTS 001 00
|
Spring-clip
|
170 XTS 002 00
|
Type
|
Number of Rows
|
Part Number
|
---|---|---|
Screw-in
|
1 - row
|
170 XTS 006 01
|
2 - row
|
170 XTS 005 01
|
|
3 - row
|
170 XTS 004 01
|
|
Spring-clip
|
1 - row
|
170 XTS 007 01
|
2 - row
|
170 XTS 008 01
|
|
3 - row
|
170 XTS 003 01
|
![]() |
POTENTIAL FOR SHORT CIRCUITS AND/OR POWER-UP SPIKES
Provide external fuses on the operating voltage to protect the module. Appropriate fuse values are shown in the wiring illustration. An unprotected module may be subject to short circuits and/or power-up spikes.
Failure to follow these instructions can result in injury or equipment damage.
|
Row
|
Connection
|
Signal
|
Meaning
|
---|---|---|---|
2
|
1, 3, 5, 7
|
U1+ ... U4+
|
pos. voltage input (analog)
|
2, 4, 6, 8
|
IS1 ... IS4
|
current sensing inputs (analog)
|
|
9, 11
|
QV1, QV2
|
analog output channels 1 ... 2 (voltage mode)
|
|
10, 12
|
QI1, QI2
|
analog outputs, channels 1 ... 2 (current mode)
|
|
13 ... 16
|
I1 ... I4
|
discrete inputs 1...4
|
|
17/ 18
|
M-/ L+
|
reference potential and operating voltage
|
|
3
|
1, 3, 5, 7
|
UI1- ... UI4-
|
neg. voltage mode and current mode inputs (analog)
|
2, 4, 6, 8
|
I1+ ... I4+
|
pos. analog inputs, channels 1 ... 4 (current mode)
|
|
9 ... 12
|
Ag
|
reference potential for analog channels
|
|
13, 14
|
O1, O2
|
discrete outputs 1,2
|
|
15, 16, 17
|
M-
|
reference potential for discrete outputs
|
|
18
|
1L+
|
output voltage mode for discrete outputs
|
|
4
|
1 ... 18
|
1L+
|
sensor supply
|
5
|
1 ... 18
|
1M-
|
reference potential for sensors
|
6
|
1 ... 18
|
PE
|
protective ground
|