4x Registers
Original instructions
Overview
The 4x registers traffic copped to this module are used for output data as follows.
I/O Map Register
Data Type
4x + 5
Data for discrete output
4x + 6
Data for analog output channel 1
4x + 7
Data for analog output channel 2
Range
Output Operating Range
Output Voltage
Data is Left Justified
Comment
Output Range
-10.000 ... +10.000
00382 ... 32382
Nominal output voltage range
Output Over Range
+10.000 ... +10.238
32384 ... 32764
Linear over range output voltage
Output Out of Range
≥10.238
32766
(7FFE Hex)
Threshold limited to 32766 decimal
Output Under Range
-10.238 ... -10.000
00002 ... 00382
Linear under voltage range
Output Out of Range
≤-10.238
00000
Threshold limited to 00000