Field Wiring Guidelines
Original instructions
Overview
This section contains wiring guidelines and precautions for wiring the 170 ANR 120 91 TSX Momentum I/O base.
Terminal Connector
To connect field devices to the I/O base, you need a field wiring terminal connector. Schneider Automation sells terminal connectors in sets of three.
Type
Part Number
Screw-in
170 XTS 001 00
Spring-clip
170 XTS 002 00
Busbar May Be Required
Depending on the type of field devices you are using, you may need a 1-, 2-, or 3- row busbar. The following busbars are available from Schneider Automation.
Type
Number of Rows
Part Number
Screw-in
1 - row
170 XTS 006 01
2 - row
170 XTS 005 01
3 - row
170 XTS 004 01
Spring-clip
1 - row
170 XTS 007 01
2 - row
170 XTS 008 01
3 - row
170 XTS 003 01
Mapping Terminal Blocks and Busbars
The following table shows mapping terminal blocks and optional busbars.
Row
Terminal
Connection
Description
2
1-4
I1 ... I4
Discrete inputs 1 through 4
5
Digital ground
Return for discrete inputs
6-9
I5 ... I8
Discrete inputs 5 through 8
10-12
AI1 ... AI3
Analog inputs 1, 2, 3
13
Analog ground
Return for analog inputs
14-16
AI4 ... AI6
Analog inputs 4, 5, 6
17
M-
Module operating voltage, 24VDC return
18
L+
Module operating voltage, 24VDC
3
1-4
O1 ... O4
Discrete outputs 1 through 4
5
1M-
Return for discrete outputs
6-9
O5 ... O8
Discrete outputs 5 through 8
10, 12, 14, 16
AO1, AO2, AO3, AO4
Analog outputs 1, 2, 3, 4
11, 13, 15
Analog ground
Return for analog outputs
17
1M-
Voltage for field devices, 24VDC return
18
1L+
Voltage for field devices, 24VDC
4
1-18
PE
Earth ground for field devices