Ident Codes for Momentum I/O Bases
 
General Information about Ident Codes
All Momentum I/O modules have an internal ident code. It is required so that a DP master can identify the types of connected devices. The master compares byte 1 of the ident code of the connected DP devices with the ident codes in the configuration data provided by the service terminal. Application data transmission begins only when the proper device types with the correct device addresses are connected to the bus. In this way, a relatively high security from configuration errors is achieved.
The ident code is visible to you only if it has been entered in the appropriate files (for Momentum modules, file ASA_7512.GSD on diskette 381 SWA 000 00). The user should always use the current GSD file.
From the ident code you can tell which module type has sent a diagnostics message.
Ident Codes for analog I/O Bases
Ident codes for analog I/O bases can be found here:
Description
Function
Ident code byte 18
Ident code byte 19
170 AAI 030 00
8 input channels
C0 hex
02 hex
170 AAI 140 00
16 input channels
C1 hex
04 hex
170 AAI 520 40
4 input channels, RTD, thermoelements
C2 hex
04 hex
170 AAO 120 00
4 output channels
C3 hex
01 hex
170 AAO 921 00
4 output channels
C4 hex
01 hex
170 AMM 090 00
4 inputs, 2 outputs (discrete)
4 input channels, 2 output channels (analog)
E0 hex
02 hex
170 ANR 120 90
8 inputs, 8 outputs (discrete)
6 input channels, 4 output channels (analog)
17 hex
E3 hex
Ident codes for special modules
Ident codes for special modules can be found here:
Description
Function
Ident code byte 18
Ident code byte 19
170 ADM 540 80
6 inputs, 3 outputs, 120 VAC;
1 Modbus interface
E2 hex
11 hex
170 AEC 920 00
Counter
A0 hex
04 hex
Ident Codes for discrete I/O Bases, 24 VDC
Ident codes for discrete I/O bases can be found here:
Description
Function
Ident code byte 18
Ident code byte 19
170 ADI 340 00
16 inputs
02 hex
00 hex
170 ADI 350 00
32 inputs
01 hex
00 hex
170 ADO 340 00
16 outputs
06 hex
00 hex
170 ADO 350 00
32 outputs
09 hex
00 hex
170 ADM 350 10
16 inputs, 16 outputs
08 hex
00 hex
170 ADM 350 11
16 inputs, 16 outputs
08 hex
00 hex
170 ADM 370 10
16 inputs, 8 outputs
0B hex
00 hex
170 ADM 390 10
16 inputs, 12 outputs
0C hex
00 hex
170 ADM 390 30
10 inputs, 8 outputs
0A hex
00 hex
Ident Codes for discrete I/O Bases, 120/230 VAC
Ident codes for discrete I/O bases can be found here:
Description
Function
Ident code byte 18
Ident code byte 19
170 ADI 540 50
16 inputs / 120 VAC
03 hex
00 hex
170 ADI 740 50
16 inputs / 240 VAC
28 hex
00 hex
170 ADO 530 50
8 outputs / 120 VAC
16 hex
00 hex
170 ADO 540 50
16 outputs / 120 VAC
14 hex
00 hex
170 ADO 730 50
8 outputs / 230 VAC
17 hex
00 hex
170 ADO 740 50
16 outputs / 230 VAC
15 hex
00 hex
170 ADM 690 50
10 inputs, 8 outputs, 120 VAC
0A hex
00 hex
170 ADM 690 51
10 inputs, 8 outputs, 120 VAC
09 hex
00 hex
170 ARM 370 30
10 inputs (24 V), 8 relay outputs
120 VAC
18 hex
00 hex